2 automatic torque boost selection (pr. 98 ), Age 125) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 135

Advertising
background image

125

Auxiliary parameters

2

F

UNCT

IO

NS

2.11.2 Automatic torque boost selection (Pr. 98

)

<Operating conditions>

•The number of motor poles should be any of 2, 4 and 6 poles.

•Single-motor operation (One motor for one inverter)

•The wiring length from inverter to motor should be within 30m.

<Setting>

• Also when the Pr. 98 setting is other than "- - -", Pr. 3 "base frequency" and Pr. 19

"base frequency voltage" are valid.

• When "- - -" or "888" is set in Pr. 19, the rated output voltage is selected.

You can choose automatic torque boost control.

Automatic torque boost control
Not only gives the motor the optimum excitation but also provides high torque
even in a low speed range.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

98

Automatic torque boost
selection (motor capacity)

- - -

0.1 to 3.7kW,

- - -

Setting is enabled when
Pr. 30 = "1"

Parameter

Setting

Description

98

- - -

Ordinary V/F control and torque boost (Pr. 0, Pr. 46) are valid.

0.1 to 3.7kW

Automatic torque boost control valid
(Set the applied motor capacity or one rank lower motor capacity.)

CAUTION

During operation using automatic torque boost, write to Pr. 3 and Pr. 19 is
disabled even if "2" is set in Pr. 77.

Related parameters

• Torque boost

Pr. 0 "torque boost", Pr. 46 "second torque boost" (refer to page 67)

• Base frequency

Pr. 3 "base frequency", Pr. 19 "base frequency voltage" (refer to page 69)

• Applied motor setting

Pr. 71 "applied motor" (refer to page 73)

• Motor primary resistance

Pr. 99 "motor primary resistance" (refer to page 126)

Advertising
This manual is related to the following products: