13 stall prevention (pr. 22 , pr. 23 , pr. 28 ) – MITSUBISHI ELECTRIC FR-S520E User Manual

Page 91

Advertising
background image

81

Explanation of functions (parameters)

2

F

UNCT

IO

NS

2.3.13 Stall prevention (Pr. 22

, Pr. 23

, Pr. 28

)

<Setting>

•Generally, set 150% (factory setting) in Pr. 22 "stall prevention operation level".

Setting "0" in Pr. 22 disables stall prevention operation.

•To reduce the stall prevention operation level in the high frequency range, set the

reduction starting frequency in Pr. 28 "stall prevention operation reduction starting
frequency" and the reduction ratio compensation factor in Pr. 23.
Formula for stall prevention operation level

•By setting "- - -" (factory setting) in Pr. 23, the stall prevention operation level is

constant at the Pr. 22 setting up to 120Hz.

Set the output current level (% value to the inverter rated current) at which the
output frequency will be adjusted to prevent the inverter from stopping due to
overcurrent etc.

During high-speed operation above the rated motor frequency, acceleration
may not be made because the motor current does not increase. To improve
the operating characteristics of the motor in this case, the stall prevention
level can be reduced in the high frequency region. This function is effective for
performing operation up to the high speed range on a centrifugal separator
etc. Normally, set 60Hz in Pr. 28 "stall prevention operation reduction starting
frequency" and 100% in Pr. 23.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

22

Stall prevention operation
level

150%

0 to 200%



Setting is
enabled
when
Pr. 30 = "1".

23

Stall prevention operation
level compensation factor at
double speed

- - -

0 to 200%,

- - -

- - -: Pr. 22

equally

28

Stall prevention operation
reduction starting frequency

60Hz

0 to 120Hz



Stall prevention operation level (%) = A + B ×[

Pr. 22-A

]×[

Pr. 23-100

]

Pr. 22-B

100

where, A =

Pr. 28 (Hz) × Pr. 22 (%)

,

B =

Pr. 28 (Hz) × Pr. 22 (%)

output frequency (Hz)

120Hz

120Hz

Pr.22

Pr.28

Pr.23

S

ta

ll pr

e

v

en

ti

on

oper

at

ion l

e

ve

l

(%

)

Output
frequency (Hz)

R

educt

io

n

r

a

ti

o

com

p

e

n

sat

ion f

a

ct

or

(%)

="- - -"

Pr.23

When

Setting example

(Pr.22=
Pr.23=100%, Pr.28= Hz)

0

80100120

Stall prevention

operation level (%)

Output
frequency (Hz)

60

90
75

60

112.5

150

150%,