VeNtING INStAllAtIoN

W

ARNING

When installing the appliance as a rear vent unit, the 90°, 45° transition elbow
attached directly to the rear of the unit is Not INCluDeD in the following
criteria and calculations, and unless specifically mentioned should be ignored
when calculating venting layouts.

•

The maximum number of 90° elbows per side wall

installation is three (3). Figure 20

•

If a 90° elbow is fitted directly on top of the fireplace

flange, the maximum horizontal vent run before the ter-
mination or a vertical rise is 36" (914 mm). Figure 21

FP1176
max 90 bends

Figure 20 -
Maximum Three (3) 90° Elbows
Per Installation

3 x 90°
Elbows

3 x 90°
Elbows

FP1176

Max 20"

Max 20"

36"

(914 mm)

Max.

36"

(914 mm)

Max.

FP1177
max horizontal run

Figure 21 -
Maximum Horizontal Run with No Rise

FP1177

•

If a 90° elbow is used in the horizontal vent run (level

height maintained) the horizontal vent length is reduced
by 36" (914 mm) (Fig. 1 A and B) This does not apply if
the 90° elbows are used to increase or redirect a vertical
rise. Figure 22

Example: According to the vent graph (page 17) the maxi-
mum horizontal vent length in a system with a 7.5' vertical
rise is 20’ (6 m) and if a 90° elbow is required in the hori-
zontal vent it must be reduced to 17' (5.2 m).
In Figures 22 and 24,
Dimension A plus B must not be
greater than 17' (5. m).

A: 10’

B: 7’

7’6”

FP1959
max run w/elbows

Figure 22 -
Maximum Vent Run with Elbows

Horizontal 90° Elbow = 3' Reduction

FP1959

A + B = 17' Maximum

A

B

7’6”

90°

FP2413
horz run reduct

Figure 23 -
Horizontal Run Reduction

FP466