3.3.3.4 Warning Set Point

S e n s o r 0 1 C O

W a r n i n g : _ _ 5 0 p p m

Figure 3-27 Sensor’s Warning Level

The default warning levels for the sensors are:

Carbon Monoxide

50 ppm

Nitrogen Dioxide

3.0 ppm

Combustible

2,000 ppm (5% LEL for methane)


Setting a warning level of 0 (zero) will disable warning detection for this particular sensor.

3.3.3.5 Range

S e n s o r 0 1 C O

R a n g e : _ 2 0 0 p p m

Figure 3-28 Sensor’s Range

The range for each sensor is the gas concentration that corresponds to the 20 mA signal level.

The default range values for the sensors are:

Carbon Monoxide

200 ppm

Nitrogen Dioxide

6.0 ppm

Combustible

10,000 ppm (25% LEL for methane)