Manitowoc Ice GR-0401W User Manual

Warning, G-0400 refrigerant field conversion procedure, For models

Advertising
background image

Manitowoc Equipment Works

Division of The Manitowoc Company, Inc. • 2110 South 26 Street, P.O. Box 1720, Manitowoc , WI 54221-1720 USA

Telephone 414-682-0161 • Fax - Sales: 414-683-7589 • Service/Parts: 414-683-7585 • Other: 414-683-7879

G-0400 REFRIGERANT FIELD

CONVERSION PROCEDURE

R-502 to R-402B

FOR MODELS


GR-0400A GR-0401W GR-0490N
GD-0402A GD-0403W GD-0492N
GY-0404A GD-0405W GY-0494N

WARNING!

Use only R-402B as

retrofit refrigerant. Other

replacement refrigerants

may cause poor performance

and/or component failure.

EQUIPMENT MODIFICATION REQUIREMENTS


Component Change Required

Compressor

None (replacement compressor is precharged with POE oil)

Expansion Valve (TXV)

None

High Pressure Cut-out

None

Low Pressure Cut-out (Remotes)

None

Fan Cycling Control (Air-cooled)

None

All Solenoid Valves

None

Water Regulating Valve (Water-cooled)

None

Heat

Exchanger

None

Electrical

Wiring

None

Branch Circuit Fuse Size

None

Air-cooled

Condenser

None

Water-cooled

Condenser

None

Evaporator

None

SYSTEM PERFORMANCE AFTER CONVERSION

Daily Ice Production Energy Efficiency

G-0400 8% increase 5% increase


Operating discharge (high) pressure: air-cooled models will run 20-30 psig (138-207 kPa gauge)
higher than R-502 pressures published in service manuals. Set water-cooled head pressure the same
as R-502 settings.

Operating suction (low) pressure: will run 1-3 psig (7-21 kPa gauge) higher than R-502 pressure
published in service manuals.


8010513
Sheet 1 of 2
08/96