Motorola 68P02958C00-B User Manual

Page 434

Advertising
background image

Error Messages

C-142

Error #270:

Incompatible Communication PROTOCOL on: PORT #%% CONTROL=%%
STATUS=%%

May indicate system software/hardware problem. Consult product group.

Error #271:

Uncontrollable Communication PHYSICAL on: PORT #%% CONTROL=%%
STATUS=%%

May indicate system software/hardware problem. Consult product group.

Error #272:

Unoperational Communication PHYSICAL on: PORT #%% CONTROL=%%
STATUS=%%

May indicate system software/hardware problem. Consult product group.

Error #273:

Unoperational PHYSICAL Internal LOOP on: PORT #%% CONTROL=%%
STATUS=%%

When checking the port (HDLC or UART), the RTU turns into a self loop
mode, sends a frame and receives it. This message is displayed if the received
frame is not equal to the one that was sent, and the port is port3.

Error #274:

Unoperational PHYSICAL External LOOP on: PORT #%% CONTROL=%%
STATUS=%%

When checking the port (HDLC or UART), the RTU turns into an internal loop
mode, sends a frame and receives it. This message is displayed if the received
frame is not equal to the one that was sent, and the ports are 1 or 2.

Error #275:

Unsuccessful PHYSICAL Configuration on: PORT #%% COMMAND=%%
ANSWER=%%

Internal modem does not exist or illegal parameters were downloaded to this
modem.

Error #276:

Uncontrollable PHYSICAL Configuration on: PORT #%% COMMAND=%%
DATA=%%

Problem in the internal modem.

Error #280:

Incompatible Communication BOARD on: PORT #%% CONTROL=%%
STATUS=%%

Piggyback on port3 is illegal.

Error #281:

Uncontrollable Communication CHANNEL on: PORT #%% CONTROL=%%
STATUS=%%

Programmable RS-232 was not defined and the CTS & RTS detectors are
defected.

Advertising