80
3.13.1.3 Output control
(1) Click [Output control] in the DIDO
controller (66DC) input/output status 
monitoring screen. 
 
 
 
 
 
 
 
 
 
 
 
 
(2) The current output status is monitored, and
Output control screen will appear.
* The pressed (sunken) button shows
the current status.
 
 
(3) Check the checkbox of the channel to be output.
(4) Click [Operation] or [Stop].
(5) Click [Send settings].
(6) The message ”Settings will be sent. OK?” will appear, click [Yes].
The setting will be applied to the unit.
 
 
 
(7) The message ”Settings have been sent.” will appear, click [OK]. 
 
 
 
 
 
(8) Click [Close] to return to the DIDO controller (66DC) input/output status monitoring screen. 
 
 