Moxa Technologies NPort 6110 User Manual

Page 32

Advertising
background image

4-11

when Auto Slave Unit ID is “Disabled.”

2. When the Modbus serial protocol is set to Modbus/RTU, each message

packet is determined by a character timeout. An incorrect character timeout

might cause a CRC checksum error. NPort Modbus Gateway allows a

variable character time out setting, ranging from 10 to 3000 ms, when the

attached serial device is set to Modbus/RTU.

3. This setting is in effect when the Modbus Gateway connects a Modbus/TCP

Master with Modbus serial slave devices. When the Modbus Gateway can’t

get a response from Modbus serial devices, the Modbus serial protocol will

not respond to the master device. However, the TCP protocol has a longer

waiting time, which could cause a network traffic problem for Modbus/TCP.

For this reason, Modbus Gateway can automatically send a Modbus

Exception Code 16 to the Modbus/TCP master device when there is no

response from the Modbus serial slave devices, making overall network

communication much more efficient.

Yes: default.

No:

No Modbus/TCP exception handling.