INSTALLATION

Open Sensor Indication

When an RTD has failed due to an open sensor (broken path in the element),
the transmitter will indicate an error. The way the error is produced is by dri-
ving the current high, above 20 mA (upscale burnout). However, the burnout
indication does not apply to breaks in the lead compensation loop.

Application Hints

The calibrated output of the Murphy Transmitter is 4.0 to 20.0 mA. However,
the lower and upper limit of output current is approximately 3.4 and 30 mA
respectively. This means that for the system using a 250 ohm resistor (1 to 5 V),
the maximum voltage could be as high as 7.5 volts (30 mA x 250 ohms) in the
case of an open RTD. Some computer-based systems will not tolerate input
voltages greater than approximately 5.5 volts. Instead of selecting a different
scaling resistor (167 ohms for example gives 5 V for an open RTD), a 5.1 V
zener diode in parallel with the scaling resistor will clamp the voltage across the
scaling resistor to 5.1 V while still allowing the calibrated range to remain 1 to 5
volts. See figure below.
The transmitter dissipates power according to the formula: Power = Volts x Amps.
The dissipated power is equal to the voltage at the transmitter’s terminals multi-

plied by the operating current. A transmitter with 24 volts at its terminal and
with maximum current (30 mA for an open RTD) will dissipate 0.7 watts of
power. This can be significant if the RTD sensor can be affected by thermal
gradients from the transmitter.

RTDT Calibration

Murphy RTD transmitter modules are factory calibrated. Please DO NOT
attempt to recalibrate unless the proper equipment is available. If recalibra-
tion is necessary, a Zero, Rlin, and Span adjustment can be made from the
top of the unit. A precision RTD simulator with a traceable calibration
must be used. Consult a book of tables for resistance values.
1. With a resistance value corresponding with the temperature at 4.0 mA,

adjust the zero potentiometer for 4.0 mA output.

2. With a resistance value corresponding with temperature at 12.0 mA,

adjust the Rlin potentiometer for 12.0 mA output.

3. With a resistance value corresponding with the temperature at 20.0 mA,

adjust the span potentiometer for 20.0 mA output.

4. The zero, Rlin and span adjustments are interactive. Repeat steps 1, 2,

and 3 as necessary.

Example 1:

1. If range equals 50 -250°, then span equals 200°
2.
Divide 200° by 2: 200° ÷ 2 = 100°
3.
Add 100° to lower end of range: 50° + 100° = 150°
4.
50° equals the Zero point (4 mA)
5. 150° equals 50% of the Span (12 mA) (Rlin)
6. 250° equals the Span point (20 mA)

Example 2:

1. Set zero at 4.0 mA for -100°F (70.95 Ω)
2. Set Rlin at 12.0 mA for 0°F (93.01 Ω)
3. Set span at 20.0 mA for 100°F (114.68 Ω)

Troubleshooting

Problem

Possible causes

No current flow on signal loop

Current loop open at some point.
No voltage out at power supply.
Wrong polarity on loop supply.

Current over 20 mA

RTD is open.
Current loop connections shorted.

Erratic readings

Loose connection in RTD or signal loop.
Damaged RTD.
AC noise on loop connections.
Exceeds loop resistance R.

Warranty

A limited warranty on materials and workmanship is given with this

FW Murphy product. A copy of the warranty may be viewed or printed by going to

www.fwmurphy.com/support/warranty.htm

Lead Compensation

250 OHMS
Sampling
Resistor

4-20 mA End of

Line Input

+ 24 VDC

RTDT

+

+

- -

- -

CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA
+1 281 633 4500 fax +1 281 633 4588
e-mail [email protected]

MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P.; México 78384
+52 444 8206264 fax +52 444 8206336
Villahermosa Office +52 993 3162117
e-mail [email protected]
www.murphymex.com.mx

FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
+44 1722 410055 fax +44 1722 410088
e-mail [email protected]
www.fwmurphy.co.uk

MURPHY SWITCH OF CALIFORNIA
41343 12th Street West
Palmdale, California 93551-1442; USA
+1 661 272 4700 fax +1 661 947 7570
e-mail [email protected]
www.murphyswitch.com

In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.

MACQUARRIE CORPORATION
1620 Hume Highway
Campbellfield, Vic 3061; Australia
+61 3 9358 5555 fax +61 3 9358 5558
e-mail [email protected]

FW Murphy
P.O. Box 470248
Tulsa, Oklahoma 74147 USA
+1 918 317 4100
fax +1 918 317 4266
e-mail [email protected]
www.fwmurphy.com

R

E

G ISTERE

D

USA–ISO 9001:2000 FM 28221

UK–ISO 9001:2000 FM 29422

Printed in U.S.A.

Advertising