2

1.1.2 On-Line Monitor(via G-50)

The On-Line Monitor is connected to the unit by the central controller(G-50A) and can monitor such areas
as system data, unit data and operating data.

(1) In case for local connection

By directly connecting the PC installed with Maintenance Tools and G-50A through LAN, various
monitoring/setting can be performed from the Maintenance Tools.









(2)-1 In case for remote connection (Dialup connection mode)

By connecting the PC installed with Maintenance Tools and G-50A through public network remotely,
various monitoring/setting can be performed from the Maintenance Tools.






(2)-2 In case for remote connection (E-mail connection mode)

Under E-mail connection mode, communication can be executed with G-50A through E-mail transmission
via mail server. All communication with G-50A is converted into E-mail in this case.


























Maintenance
Tools PC

G-50A

LAN

HUB

M-NET

M-NET

MODEM etc

Public

network

Dial-up

Router

Maintenance
Tool PC

HUB

G-50A

LAN

Maintenance
Tools PC

LAN

G-50A

POP

Internet

Provider 2
Access point

Provider 1
Access point

Provider1
Mail server

Provider2
Mail server

SMTP

POP

SMTP

Mail server

Mail server

E-mail

E-mail

Notice

•To use the E-mail connection mode, the version of G-50 should be above 2.60.

•When using E-mail connection mode, the local G-50A is required to be initially set with Maintenance Tool and
the mail address by the G-50A initial setting tool.

- For each mail address, it is required to obtain and set an exclusive one. To transmit mail via an internet

provider, obtain the mail address from the provider. When a mail server is existing on the LAN, obtain the
mail address from the LAN administrator.

- Set the [Pop receive interval] within 3 minutes. However to monitor operating status [Operation Monitor], set it within 1

minute.

- Setting of initial information to G-50A can not be executed from Maintenance Tool. Make sure to set it from the G-50A

initial setting tool locally. If dialup connection environment is available, it can be set from a remote position.
(For detail, please refer to 6-1 Mail Basic Setting in the instruction manual of the G-50A initial setting tool.)

• The communication speed under E-mail connection mode largely depends on the transfer rate of each mail

server. Under the circumstance, the action of Maintenance Tool may take a lot of time under some internet
environments or routing mail servers.