MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 97

Advertising
background image

–95–

1

LEV

Note 1 :

Symptoms of incorrect connection to BC controller LEV board

Improper installation is the same for

1

and

2

, so it is omitted here.

Note 2 : Method for checking LEV full open, full closed condition

1

Check LEV full opening (pulse) using the LED monitor display (outdoor controller board SW1).

Full opened: 2000 pulses

Full closed: 60 pulses (LEV 1 may be greater than 60 during full heating operation.)

2

With LEV full opened, check for pressure differential by measuring temperature of piping on both sides.

3

With LEV full closed, check for refrigerant noise.

Note 3 : Use the following table to determine opening due to LEV differential pressure control and superheat

control.

BC controller LEV basic operation characteristics

LEV No.

1

3

Cooling-only

Cooling-main

Heating-only

Heating-main

1)

1

3

Normal

2)

3

1

Insufficient cooling
SH12 small,
SC11 small
SC16 small
Branch piping SC small

Insufficient cooling, insuf-
ficient heating
SH12 small, SC11 small
SC16 large,
Branch piping SC small

PHM large

Heating indoor SC small

PHM large

Insufficient cooling
Heating indoor SC small

PHM large

Small

Large

Small

Large

High pressure (PS1) - medium pressure (PS3) is large.

High pressure (PS1) - medium pressure (PS3) is small.

SH12 is large.

High pressure (PS1) - mid pressure (PS3) is small.

SC16 and SH12 are small.

High pressure (PS1) - mid pressure (PS3) is large.

Heating-only
Heating-main
Cooling-main

Cooling-only
Cooling-main
Heating-only
Heating-main

Cooling-only
Cooling-main

Heating-only
Heating-main

2.0 ~ 3.5 kg/cm

2

G

(0.20~0.34MPa)

SH12<25

2.0 ~ 3.5 kg/cm

2

G

(0.20~0.34MPa)

SC16>6
SH12>5

2.0 ~ 3.5 kg/cm

2

G

(0.20~0.34MPa)

LEV1

pulse

LEV3

pulse

Region

Failure mode Operating mode

Description

Normal range

LEV3a

pulse

*

Small

FA

FB

Cooling-only
Cooling-main
Heating-main

Cooling-only
Cooling-main
Heating-main

SH22 is large.

SH22 is small.

SH22<25

SH12>5

* LEV3a operates when indoor unit connected to FB type is cooling mode.