Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual

Page 60

Advertising
background image

Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.

Configuration for

Configuration for

Configuration for

2 hours backup time

4 hours backup time

8 hours backup time

EX 5

7 hours

15 hours

24 hours

EX 7

5 hours

12 hours

20 hours

EX 11

7 hours

15 hours

24 hours

5.4

System Short Circuit Protection

Short circuit current provided by EX 5/7/11RT in normal or battery mode:

EX5/7 RT

110A for 80ms

EX11 RT

190A for 80ms

5.5

Accessories Electrical Characteristics

EX RT Transformer

Nominal power

11 kVA

Nominal current

63 A

Input voltage

208-240Vac

Output Voltage

120/208/240Vac

Frequency

50/60 Hz (+/-10%)

Isolation (EN 61558-1-2-4)

3.75 kV / 5 M ohms

Operating temperature

From 0° to +40°C

Max. operating rel. humidity

95%

Derating / altitude

Pn-10% > 1000 m

Dimensions HxWxD (tower)

17.5 x 5.15 x 25 inches (444 x 131 x 635 mm)

Dimensions HxWxD (rack 3U)

5.15 x 17.5 x 25 inches (131 x 444 x 635 mm)

Weight

151 lbs. (68.5 kg)

EX RT CLA module

AC input voltage

156-280 Volts AC

Input frequency

40-70 Hz

Battery charge current

6 A DC

5.6

Heat Rejection

Table 5-4: Full load heat rejection in BTU’s/hr.

System

Operation Mode

On-line

On Battery

5kVA

1327

1944

7kVA

1858

2722

11kVA

2919

4278

5.7

Environmental Characteristics

◗

The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C
range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.

◗

The storage temperature : -20 to 40°C. Humidity : 5-95%, non condensing.

◗

Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-
tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers
no longer guarantee operation due to the risk of thermal runaway.

◗

Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.

EX 5/7/11 RT System

Appendix

5 — 2

86-86000-00 A01