PERFORMANCE DATA – NOZZLES
Mounting Height, Heat Throw, Heat Spread (in feet)
S
T
H
S
S
H
S
T
T
H
S
S
40° DOWNWARD
NOZZLE
40° SPLITTER
NOZZLE
90° VERTICAL
NOZZLE
5-WAY
NOZZLES
Max. Mounting Ht. (ft.) H
14
16
18
22
21
24
27
24
26
28
32
32
Heat Throw (ft.) T
41
49
54
66
63
72
81
71
78
83
96
96
Heat Spread (ft.) S
14
16
18
22
21
24
27
24
26
28
32
32
Max. Mounting Ht. (ft.) H
15
17
18
22
22
21
24
24
26
28
32
32
Heat Spread (ft.) S
15
17
18
22
22
21
24
24
26
28
32
32
Max. Mounting Ht. (ft.) H
–
–
16
20
20
21
24
21
23
26
30
32
Heat Throw (ft.) T
–
–
41
50
49
52
59
53
58
65
75
80
Heat Spread (ft.) S
–
–
81
100
97
104
117
106
116
129
151
160
Max. Mounting Ht. (ft.) H
12
14
15
18
17
18
20
20
21
20
23
26
Heat Spread (ft.) S
17
20
21
26
24
25
28
27
30
27
32
37
BAE-50 BAE-75 BAE-100 BAE-125 BAE-145 BAE-175 BAE-200 BAE-225 BAE-250 BAE-300 BAE-350 BAE-400
Model Number
40°
Downward
Nozzle
90° Vertical
Nozzle
40° Splitter
Nozzle
5-Way
Nozzle
Nozzle
Type
The above table is based on an inlet air temperature of 70°F and an air temperature rise of 55°F. Air deflectors on, 40° and 90° discharge nozzles set perpendicular to
the face of the air discharge opening. On 5-way nozzles all air deflectors set perpendicular to floor. Static pressure measured at 0.1" W.C. for 90° nozzle, 0.2" W.C. for
40° downward and 5-way nozzle, and 0.3" W.C. for 40° splitter nozzle. Outlet velocities are approximately 1750 FPM for the 40° nozzles, 1000 FPM for the 90° nozzle
and 1300 FPM for 5-way. For motor size, drive and blower rpm refer to pages 18 and 19. Mounting height measured from bottom of unit.
A choice of four air discharge nozzles 
accommodate various heat throw 
patterns illustrated. Equipped with 
adjustable louver blades, nozzles 
are fabricated from galvanized 
steel and are offered either 
unpainted or painted to match 
the finish of the blower unit 
heaters. Nozzles are flanged 
for easy attachment over 
the air discharge opening 