Technical data – MGE UPS Systems ESV 11+Rack User Manual
Page 21

MGE UPS SYSTEMS
Pulsar ESV 8+Rack/11+Rack/14+Rack/22+Rack
: 86-153523-00
21
technical data
■
output power:
■
■
Pulsar ESV 8+
Rack:
780VA/490W
■
■
Pulsar ESV 14+
Rack: 1400VA/980W
■
■
Pulsar ESV 11+
Rack
1080VA/700W
■
■
Pulsar ESV 22+
Rack: 2200VA/1540W
■
utility power source:
■
■
voltage (V):
92V to 138V single phase (*)
■
■
frequency (F):
47Hz to 53Hz or 57Hz to 63Hz
■
battery:
Pulsar ESV 8+
Rack: 2 x 12V - 7.2Ah
■
■
type:
Pulsar ESV 11+
Rack: 3 x 12V - 7.2Ah
Pulsar ESV 14+
Rack: 4 x 12V - 7.2Ah
Pulsar ESV 22+
Rack: 8 x 6V - 12Ah
maintenance free sealed lead-acid
caution: battery life (4 or 5 years) is halved every 10°C above 25°C
■
output specifications with load on battery:
■
■
voltage (V):
single phase 120V ±5% (**)
■
■
frequency (F):
50Hz/60Hz ± .1Hz auto selection
■
output specifications with load on utility power:
■
■
voltage (V):
see "normal operation with utility power present"
■
■
frequency (F):
47Hz to 53Hz or 57Hz to 63Hz
■
environment:
■
■
noise level:
≤
40dBA for operation on utility power
≤
45dBA for battery backup time
■
■
operating temperature:
0 to 35°C
■
■
relative humidity:
0 to 90% non condensing
■
dimensions and weights:
Pulsar ESV 8+
Rack / 11+Rack / 14+Rack
Pulsar ESV 22+
Rack
■
■
height H (mm/inch):
133.35/5.25
177.8/7
■
■
width W (mm/inch):
482.6/19
482.6/19
■
■
depth D (mm/inch):
457.2/18
457.2/18
■
■
weight (kg/lb) :
25/29/31 (kg) 55/64/68 (lbs)
44/97
(*): adjustable high and low thresholds using ESV Driver (CD-ROM: EMB/ESVPLUS/CONFIG)