FAULT FINDING

FAUL

T FINDING FAUL

T FINDING FAUL

T FINDING FAUL

T FINDING FAUL

T FINDING FAUL

T FINDING

31

Concord CXSi/H -

Installation & Servicing

Is there a spark at the electrode?

Are the gas valve electrical plugs clean and secure?

42 BOILER DOES NOT LIGHT

Before carrying out any Fault Finding, ensure that all internal controls are calling for heat and that the overheat thermostat has not
operated. There should be 230V ± 10% available at the control box connection.

Is the spark gap approximately 4mm and are the

electrodes, leads and connections clean and secure?

NO

YES

YES

Is there 230V

±

10% at the gas valve plugs?

Is the gas valve inlet pressure sufficient?

Replace the gas valve

YES

YES

Are connections sound at

the plug-on terminal strip

at the control box?

YES

Is there 230V

±

10% at the spark generator

Replace

spark generator

Replace

PCB S4561B1047

YES

YES

43 BOILER LIGHTS BUT GOES TO LOCKOUT

NO

Measure the flame current - expect approximately 3.5

µA

Replace PCB S4561B1047

Check LH end burner, inlet and burner pressure; check

the LH end burner injector

YES

44 BOILER GOES OUT ON OVERHEAT THERMOSTAT

NO

YES

Is the flame detector and its lead and connections sound

and secure and correctly positioned on the LH end

burner?

YES

NO

Clean and secure

NO

Is there an unswitched Live supply to terminal L1 on

the plug-on terminal connection at the control box?

YES

Is there sufficient open circuit water volume or load

available on boiler shutdown for the pump overrun?

YES

Is the pump (or shunt pump) wired to terminal L2

in the control box?

NO

Has the boiler thermostat knob been switched to OFF?

Replace PCB W4115A1020

Refer to Installation Instructions for details

YES

Advise USER