Intel Entry Redundant Power 2U ERP2U User Manual
Page 22
 
SSI
ERP2U Power Supply Design Guide, V1.0
- 22 -
Table 19: Turn On/Off Timing
Item
Description
MIN
MAX
UNITS
T
sb_on_delay
Delay from AC being applied to 5 VSB being 
within regulation. 
1500
ms
T
ac_on_delay
Delay from AC being applied to all output voltages 
being within regulation. 
2500
ms
T
vout_holdup
Time all output voltages stay within regulation 
after loss of AC. 
18
ms
T
pwok_holdup
Delay from loss of AC to deassertion of PWOK.
17
ms
T
pson_on_delay
Delay from PSON
#
active to output voltages within
regulation limits.
5
400
ms
T
pson_pwok
Delay from PSON
#
deactive to PWOK being
deasserted.
50
ms
T
pwok_on
Delay from output voltages within regulation limits 
to PWOK asserted at turn on. 
200
1000
ms
T
pwok_off
Delay from PWOK deasserted to output voltages 
(3.3 V, 5 V, 12 V, -12 V) dropping out of regulation 
limits. 
1
ms
T
pwok_low
Duration of PWOK being in the deasserted state 
during an off/on cycle using AC or the PSON# 
signal. 
100
ms
T
sb_vout
Delay from 5 VSB being in regulation to O/Ps 
being in regulation at AC turn o n. 
50
1000
ms
STATUS
Recommended
Item
Description
MIN
MAX
UNITS
T
vout_holdup
Time all output voltages stay within regulation 
after loss of AC. 
21
ms
T
pwok_holdup
Delay from loss of AC to deassertion of PWOK.
20
ms
T
sb_holdup
Time 5VSB output voltage stays within regulation 
after loss of AC. 
70
ms