Condensing – IDEAL INDUSTRIES 36 User Manual

Page 8

Advertising
background image

8

condensing

Natural gas fired condensing boiler

Meets Building Regulations 2006 (Part L2)

Fully condensing high efficiency 85%
at 80˚C, 93% at 60˚C flow

Compact space saving design

Full automatic ignition

Advanced electronic controls

Model 48

70

94

116

Boiler output (condensing)

48.83

69.84

93.65

116.25

50/30˚C

Boiler output (non-condensing)

44.63

63.84

83.60

106.30

80/60˚C

Height

1438

Width

600

Depth

723

846

969

1092

Flow/Return Connections (BSP)

RC2

Gas Inlet (BSP)

RC

3

/

4

RC

3

/

4

RC

3

/

4

RC1

Flue Size (mm)

150

Maximum Working Pressure (bar)

4.5

Water Content (L)

28

36

43

51

Approx Dry Weight (kg)

298

350

442

494

Front (mm)

750

Back (mm)

200

Side (mm)

50

50

50

100

General Data Concord CXC (48 - 116)

Option Kits

Boiler

Remote indication board

Outside sensor

Concord CXC

Concord CXC

48 - 116kW

Boiler
Clearances

Advertising