10

N

OTE

: S

ETTINGS ARE MADE THROUGH THE SUPPLIED

P

OWER

C

HUTE SOFTWARE OR

O

PTIONAL

S

MART

S

LOT ACCESSORY CARDS

. R

EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

High Transfer Point

750TLV, 1000TLV
and 1500TLV mod-
els:127AC

750THV, 1000THV
and 1500THV mod-
els:253VAC

750TLV, 1000TLV
and 1500TLV models:
127, 130, 133, 136VAC

750THV, 1000THV
and 1500THV models:
253, 257, 261, 265VAC

If the utility voltage is usually high and the
connected equipment is specified to operate
with input voltages this high, set the high
transfer point higher to avoid unnecessary
battery usage.

Low Transfer Point

750TLV, 1000TLV
and 1500TLV mod-
els:106VAC

750THV, 1000THV
and 1500THV mod-
els:208VAC

750TLV, 1000TLV
and 1500TLV models:
97, 100, 103, 106VAC

750THV, 1000THV
and 1500THV models:
196, 200, 204, 208VAC

If the utility voltage is usually low and the
connected equipment is specified to operate
with input voltages this low, set the low
transfer point lower.