Fixing an internal jam – IBM Partner Pavilion T400F User Manual

Page 100

Advertising
background image

Fixing an Internal Jam

Attention:

This procedure must be performed only by trained service personnel.

If problem-determination procedures identify the Ultrium 2 Tape Drive as
the source of a problem, replace the entire unit. If you are not a trained
service person, do not attempt to open the drive for repairs. Attempting a
repair other than the manual removal of a tape cartridge will void your
warranty.

Before performing this procedure, ensure that you have completed the steps
that begin on page 86. Do not attempt this procedure until you have completed
these steps.

If you have reached this point, the tape is broken or the leader pin dropped (or
looked like it dropped) from the leader block. To fix these conditions, perform the
following procedure.

1. If the drive is mounted in an enclosure, perform the procedure to remove it

(see “Removing a SCSI Tape Drive from an Enclosure” on page 83 or
“Removing a Fibre Channel Tape Drive from an Enclosure” on page 84).

2. Place the drive on a nonslip surface.

3. Remove the cover of the drive by performing the following steps:

a. Use an appropriate tool to remove the three screws and washers (see

1

in Figure 31 on page 89) that secure the bezel

2 . Remove the bezel.

b. Use a screwdriver to remove the four cover-mounting screws and washers

3 .

c. Remove the cover by lifting it up. Set the cover aside.

88

IBM TotalStorage LTO Ultrium 2 Tape Drive