Instructions for the installer, Ie gb – Indesit KP9507EB User Manual

Page 8

Advertising
background image

6

IE

GB

INSTRUCTIONS FOR THE INSTALLER

Kitchen ventilation
The air flow into the room where the appliance is installed
must equal the quantity of air that is required for regular
combustion of the gas and for ventilating the same room.
Air must be taken in naturally through permanent apertures
made in the outside walls of the room or through single or
branching collective ventilation ducts in compliance with
the standards in force.

The air must be taken directly from the outside, from an
area far from sources of pollution.

The ventilation aperture must have the following
characteristics (fig.7A):
· total free cross section of passage of at least 6 cm² for

every kW of rated heating capacity of the appliance, with
a minimum of 100 cm² (the heating capacity is indicated
on the rating plate);

· it must be made in such a way that the aperture, both on

the inside and outside of the wall, cannot be obstructed;

· it must be protected, e.g. with grills, wire mesh, etc. in

such a way that the above-mentioned free section is not
reduced;

· it must be situated as near to floor level as possible.

The air inflow may also be obtained from an adjoining room,
provided the latter is not a bedroom or a room where there
is a risk of fire, such as garages, mews, fuel stores, etc.
and is ventilated in compliance with the standards in force.
Air from the adjoining room to the one to be ventilated may
be made to freely pass through permanent apertures with
a cross section at least equal to that indicated above. These
apertures may also be obtained by increasing the gap
between the door and the floor (fig.7B).
If an electric fan is used for extracting the combustion
products, the ventilation aperture must be increased in
relation to its maximum performance. The electric fan should
have a sufficient capacity to guarantee an hourly exchange
of air equal to 3-5 times the volume of the kitchen.

A

Detail A

Adjacent

Room to be

room

ventilated

Examples of ventilation holes

Enlarging the ventilation slot

for comburant air

between window and floor

fig. 7A

fig. 7B

The following instructions are provided for qualified installers
so that they may accomplish installation, adjustment and
technical maintenance operations correctly and in
compliance with current regulations and standards.
Important: the appliance should be disconnected from
the mains electricity supply before any adjustment,
maintenance, etc. is carried out.
Maximum caution should
be used whenever it is necessary to keep the appliance
connected to the electricity supply.
The cookers have the following technical specifications:
Category: II 2H3+ Class: 1
The dimensions of the appliance are given in figure on
page 2. For trouble-free operation of appliances installed
between housing units, the minimum distances shown in
fig.5 should be observed. Adjacent surfaces and the wall
at the rear should also be able to withstand a temperature
of 65 °C. In the lower part of the cooker there are 4 height
adjustable screw-in feet with which it is possible to level
the cooker if necessary.

Positioning
This appliance may only be installed and operated in
permanently ventilated rooms in compliance with provisions
laid down by current regulations and standards. The
following requirements must be observed:

• The appliance must discharge combustion products into

a special hood, which must be connected to a chimney,
flue pipe or directly to the outside (fig.6).

• If it is impossible to fit a hood, the use of an electric fan

is permitted, either installed on a window or on an external
wall, which must be switched on at the same time as the
appliance.

fig.5

fig.6

In a chimney stack or branched flue

Directly to the outside

(exclusively for cooking appliances)

Advertising