Rack pdu specifications – IBM PC Server/Enterprise Racks 42S User Manual

Page 162

Advertising
background image

154

Hardware Maintenance Manual: IBM PC Server/Enterprise Racks

Rack PDU specifications

When connected to a dedicated power source, the Rack PDU conforms to UL950, CSA
22.0-950, EN-60950, and IEC-950 standards. The following table contains the product
specifications for the Rack PDU:

Height

43 mm (1.7 in.)

Width

192 mm (7.5 in.)

Depth

221 mm (8.7 in.)

Weight

1.5 kg (3.2 lbs)

Operating temperatures

10

°

C–35

°

C (50

°

F–95

°

F) at 0–914 m (0–3000 ft)

10

°

C–32

°

C (50

°

F–90

°

F

°

)

at 914–2133 m (3000–7000 ft)

Operating humidity

8–80% (non-condensing)

Rated voltage

100–240 V ac, 15 A, single-phase

Rated frequency

50–60 Hz

Maximum power rating

3600 VA

Circuit breaker

Two-pole, 15 A with time-delay protection for up to 600 A
input current without nuisance tripping.

Power inlet

IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)

Power outlets

Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)

Advertising