NetBAY Power Distribution Units

165

Line cords

The 2.5 m (8.2 ft) fixed line cord on the Rack PDU determines the connectivity of the
Rack PDU. The following table contains a list of the line cords that you can use with
the Rack PDU:

Power cables

The Rack PDU comes with three power cables, that you use to connect to other
M/PDU family devices, as listed in the following table:

Height

43 mm (1.7 in.)

Width

192 mm (7.5 in.)

Depth

221 mm (8.7 in.)

Weight

1.6 kg (3.5 lbs)

Operating temperatures

10

°

C–35

°

C (50

°

F–95

°

F) at 0–914 m (0–3000 ft)

10

°

C–32

°

C (50

°

F–90

°

F

°

)

at 914–2133 m (3000–7000 ft)

Operating humidity

8–80% (non-condensing)

Rated voltage

100–120 V ac, 30 A, single-phase

200–240 V ac, 30 A, single-phase

200–240 V ac, 32 A, single-phase

200–240 V ac, 30 A, single-phase

380–415 V ac, 32 A, single-phase

Rated frequency

50–60 Hz

Maximum power rating

4800-6000 VA

Power inlet

One fixed line cord

Power outlets

Three IEC 320-C19 outlets rated at 16 A (VDE) / 20 A
(UL/CSA)

Power Source

Line cord rating

Plug type

Line cord

part #

100-127 V ac, 30 A, single-phase

127 V, 30 A

NEMA L5-30P

24P6846

200-240 V ac, 30 A, single-phase

250 V, 30 A

NEMA L6-30P

24P6847

200-240 V ac, 32 A, single-phase

250 V, 32 A

IEC 309-2P + Gnd

24P6848

200-240 V ac, 30 A, three-phase

250 V, 30 A

NEMA L21-30P

24P6844

380-415 V ac, 32 A, three-phase

415 V, 32 A

IEC 309-3P + N + Gnd

24P6845