Rack pdu specifications – IBM PC Server/Enterprise Racks 42S User Manual

Page 187

Advertising
background image

NetBAY Power Distribution Units

179

Rack PDU specifications

When connected to a dedicated power source, the Rack PDU conforms to UL950, CSA
22.0-950, EN-60950, and IEC-950 standards. The following table contains the product
specifications for the Rack PDU:

Height

43 mm (1.7 in.)

Width

192 mm (7.5 in.)

Depth

221 mm (8.7 in.)

Weight

2.4 kg (5.4 lbs)

Operating temperatures

10

°

C–35

°

C (50

°

F–95

°

F) at 0–914 m (0–3000 ft)

10

°

C–32

°

C (50

°

F–90

°

F

°

)

at 914–2133 m (3000–7000 ft)

Operating humidity

8–80% (non-condensing)

Rated voltage

100–127 V ac, 15 A, single-phase

200-240 V ac, 10 A, single-phase

Rated frequency

50–60 Hz

Maximum power rating

2400 VA

Power inlet

Two IEC 320-C20 inlets rated at 16 A (VDE) / 20 A (UL/CSA)

Transfer time

<35 ms from main to backup power

Power outlets

Four IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)

Advertising