Johnson Controls 13 SEER User Manual

Page 8

Advertising
background image

347337-UIM-A-0408

8

Johnson Controls Unitary Products

FIGURE 10: Thermostat Chart - Single Stage AC with PSC Air Handler

AC 1B

Single Stage Air Conditioner – PSC Air Handler

C

24 – Volt Common

Y

Compressor Contactor

SINGLE STAGE

AIR

CONDITIONER

MA

SHP

AHP

ID MODELS

SINGLE STAGE

AIR CONDITIONER

Other Part Numbers:

SAP = Legacy

265902 = 031-09167

2

Part Numbers:

SAP = Legacy

159480 = 031-09156

1

COM

24 – Volt Common

R

24 – Volt Hot

W2

Second Stage Heat

O

Reversing Valve

Energized in Cool

X/L

Malfunction Light

HUM

Humidity Switch

Open on Humidity Rise

PSC

AIR HANDLER CONTROL

G

Fan

PSC

AIR HANDLER

1

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT

(24 VAC out)

Humidifier

Y1

Single Stage Compressor

Y/Y2

Second or Full

Stage Compressor

W1

First Stage Heat

Y

Full Stage Compressor

G

Fan

*BP11C50124

*BN11C01124
*DP11C40124

*DN11C00124

THERMOSTAT

RH

24 – Volt Hot

(Heat XFMR)

RC

24 – Volt Hot
(Cool XFMR)

W

Full Stage Heat

Selection of GAS/ELEC

switch on thermostat

is not necessary

C

24 – Volt Common

Y

Full Stage Compressor

G

Fan

*BN11C00124

THERMOSTAT

RH

24 – Volt Hot

(Heat XFMR)

RC

24 – Volt Hot
(Cool XFMR)

W

Full Stage Heat

Thermostat Installer Setup

1-System Type-must be

set to 0

C

24 – Volt Common

Thermostat Installer Setup
15-Compressor Protection

must be set to 5

24VAC Humidifier

(Optional)

24VAC

Electronic Air Cleaner

(Optional)

External Humidistat

(Optional)

Open on Humidity Rise

Part Number:

S1-2HU16700124

2

2

Move HUM STAT

jumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electric

heat staging options.

Advertising