Step 6, Detailed setup, 5 alarm setup screen – JVC DM-NC40 User Manual

Page 38: Continued)

Advertising
background image

38

Step 6

Detailed Setup

(Continued)

Send To

Item

Content

Default value

IP Address

Set the address to send the alarm information.

Blank

Up to 2 destination addresses can be specified.

Port

Set the port number to send the alarm information.

10000

The maximum value is 65535.

Data

Set the sending data. Up to 64 characters can be entered.

data

Protocol

Set the transmission protocol:

TCP

TCP: Alarm information is sent by TCP.

Character string entered in Data will be sent to the

set port no.

Some custom application software may be required

to receive the alarm information by TCP.

API: Select when sending the alarm information to

monitor side DM-NC40 for automatic connection.

Port is set to “-----” (default) and Data is set to

“Disable”.

6-5 ALARM SETUP screen

(Continued)

Item

Content

Default value

Input Pin

1

* Following settings are to

be performed for each pin.

Trigger

Disabled

Trigger Duration

100ms

Recording Duration

Before Trigger

10s

After Trigger

20s

Comment

Input characters must be alphanumerical characters

dm-nc40

with a maximum of 64 characters.

Select the pin no. of the alarm port to set.

[Variable: 1~4]

Select the polarity of the alarm input signal.

Input signal is invalid when setting to Disable.

[Variable: Low, High, Disabled]

Set the length of input signal to assume as an alarm.

[Variable: 50ms, 100ms, 200ms, 300ms, 400ms, 500ms]

CF recording duration triggered by alarm is set. Duration

before the alarm and duration after the alarm are set.

The maximum time for CF recording triggered by one alarm

is 30 seconds. (Set so that the total time of Before Trigger

and After Trigger is 30 seconds or less.)

0 cannot be set for both Before Trigger and After Trigger.

* For CF recording, set JPEG in the ENCODE PARAMETERS

screen to “Video In 1” or “Video In 2”. (See page 32)

* Recording will be made before and after for about 1 sec-

ond even when setting to 0s.

Set the length of time of CF recording before alarm input.

[Variable: 0s, 5s, 10s, 15s, 20s] (Unit: sec)

Set the length of time of CF recording after alarm input.

[Variable: 0s, 5s, 10s, 15s, 20s] (Unit: sec)

* When clicking

with Comment and Data left blank, an underscore (_) will be inserted automatically.