Johnson Controls Unitary Products

OPERATING INSTRUCTIONS

1.

STOP! Read the safety information above for your protection.

2.

Set the thermostat to the lowest setting in the heat mode.

3.

Turn off all electric power to the appliance.

4.

Remove furnace burner access panel/door.

5.

Move gas control switch to the “OFF” position. Do not force. See
Figures 8, 7 or 8.

6.

Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow “B” in the safety information above. If you don’t
smell gas, go to next step.

7.

Move gas control switch to the “ON” position. Do not force. See
Figures 8, 7 or 8.

8.

Replace furnace burner access panel/door.

9.

Turn on all electric power to the appliance.

10. Set thermostat to the desired setting. Burner will light, which may

take 30-60 seconds.

11.

After three (3) trials for ignition, if the appliance will not operate fol-
low the instructions, “TO TURN OFF THE APPLIANCE” and call
your service technician or gas supplier.

TO TURN OFF THE APPLIANCE

1.

Set the thermostat to lowest setting in heating mode.

2.

Turn off all electric power to the appliance if service is to be per-
formed.

3.

Remove furnace burner access panel/door.

4.

Move gas control switch to the “OFF” position. See Figures 8, 7 or
8.

5.

Replace furnace burner access panel/door.

SECTION IV: FURNACE MAINTENANCE -

USER INFORMATION

EXTERNAL AIR FILTERS

Filters used with this furnace must be installed external to the furnace
casing. DO NOT attempt to install filters inside the furnace cabinet.

Some installations may have the air filter in a rack attached to the cas-
ing of the furnace or placed in the return air duct. If the filter location or
replacement process is not obvious, contact your installer or service
technician for assistance.

Should overheating occur, or the gas valve fail to shut off, turn
the external manual gas valve in the gas supply line to the fur-
nace to the “off” position and let the furnace cool off before
shutting off the electrical power supply.

FIGURE 8: Single Stage Gas Valve

Inlet

Wrench
Boss

Inlet
Pressure
Port

ON

OFF

On/Off Switch
(Shown in ON position)

Main Regulator
Adjustment

Outlet

Outlet
Pressure
Port

Vent Port

FIGURE 9: Two-Stage Gas Valve

FIGURE 10: Modulating Gas Valve

FIGURE 11: Gas Piping

Before proceeding, be sure the area is well ventilated. Turn the
thermostat OFF. If the blower is running, wait until it stops auto-
matically. Turn OFF the gas and electrical power supplies to the
furnace. Check all metal parts and surfaces to be sure they
have cooled to room temperature before you begin.

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON OFF
SWITCH

LOW STAGE REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT
PORT

HIGH STAGE REGULATOR
ADJUSTMENT

Inlet
Pressure
Tap

Outlet
Pressure
Tap

On/Off
Knob

Main
Regulator
Adjustment

External Manual
Shutoff Valve

To Gas
Supply

To Gas
Supply

Grounded Joint Union

may be Installed

Inside or Outside Unit.

Drip Leg