2h-heading2 - checking supply air cfm, Checking supply air cfm, 12 gase rate - cubic feet per hour – Johnson Controls 341426-BIM-A-0108 User Manual

Page 18: Table 12: gase rate - cubic feet per hour

Advertising
background image

341426-BIM-A-0108

18

Johnson Controls Unitary Products

CHECKING SUPPLY AIR CFM

To check the supply air CFM after the initial balancing
has been completed:

1.

Remove the two ¼ inch dot plugs in the duct panel.

2.

Insert at least 8 inches of ¼ inch tubing into each of
these holes for sufficient penetration into the airflow on
both sides of the indoor coil.

3.

Using an inclined manometer, determine the pressure
drop across the dry evaporator coil. Since the moisture
on an evaporator coil may vary greatly, measuring the
pressure drop across a wet coil under field conditions
would be inaccurate. To ensure a dry coil, the compres-
sors should be deactivated while the test is being run.

4.

Knowing the pressure drop across a dry coil, the actual
CFM through the unit can be determined from the curve
in Coil Delta P vs. Supply Air CFM figure.

After readings have been obtained, remove the tubes and
reinstall the two ¼ inch plugs removed in Step 1.

De-energize the compressors before taking any test mea-
surements to ensure a dry indoor coil.

TABLE 12: GASE RATE - CUBIC FEET PER HOUR

1

1.

EXAMPLE: By actual measurement, it takes 38 seconds for the
hand on the 1-cubic foot dial to make a revolution with just a
100,000 BTUH furnace running. Using this information, locate
38 seconds in the first column of Table 12. Read across to the
column headed “1 Cubic Foot,” where you will see that 95 cubic
feet of gas per hour are consumed by the furnace at that rate.
Multiply 95 x 1050 (the BTU rating of the gas obtained from the
local gas company). The result is 99,750 BTUH, which is close
to the 100,000 BTUH rating of the furnace.

SECONDS

FOR ONE

REV.

SIZE OF TEST DIAL

1/2 CU. FT.

1 CU. FT.

10

180

360

12

150

300

14

129

257

16

113

225

18

100

200

20

90

180

22

82

164

24

75

150

26

69

138

28

64

129

30

60

120

32

56

113

34

53

106

36

50

100

38

47

95

40

45

90

42

43

86

44

41

82

46

39

78

48

37

75

50

36

72

52

35

69

54

34

67

56

32

64

58

31

62

60

30

60

Failure to properly adjust the total system air quan-
tity can result in extensive system damage.

Advertising