COIL FLANGE INSTALLATION

The coils include removable flanges to allow proper fit up with furnaces
having various inlet and outlet flange configurations. The two flanges
are attached to the top of the coil in the factory during production. For
proper configuration of flanges refer to Figure 3, "Coil Flange".

FURNACE ASSEMBLY - MC SERIES COILS ONLY

MC coils are supplied ready to be installed in a horizontal position. A
horizontal pan is factory installed. MC coils should be installed in all hor-
izontal applications with the horizontal drain pan side down.

For horizontal left hand applications no conversion is required to an MC
coil when used with a downflow/horizontal furnace. A mounting plate,
supplied with every coil should always be installed on the side desig-
nated as top side. See Figures 4 & 5.

FURNACE ASSEMBLY - PC SERIES COILS

These upflow coils are designed for installation on top of upflow fur-
naces only.

If the coil is used with a furnace of a different size, use a 45° transition
to allow proper air distribution through the coil.

1.

Position the coil casing over the furnace opening as shown in Fig-
ure 6, "PC Series Upflow Coil Installation".

2.

Place the ductwork over the coil casing flange and secure.

3.

Check for air leakage between the furnace and coil casing and
seal appropriately.

NOTE: Dimension “C” should be at least 2/3 of dimension “D”. See Fig-
ure 6, "PC Series Upflow Coil Installation"

CRITICAL COIL PROJECTION

The coil assembly must be located in the duct such that a minimum dis-
tance is maintained between the top of the coil and the top of the duct.
Refer to Table 6.

COIL / FURNACE ASSEMBLY - HC SERIES COILS

These coils are supplied ready to be installed in a right hand position or
a left hand position. When used in conjunction with a horizontal furnace
(blow through) application, the coil should be oriented with the opening
of the “A” coil closest to the furnace. See Figure 6.

NOTE: Each coil is shipped with an external tie plate that should be
used to secure the coil to the furnace. It should be installed on the back
side of the coil using the dimpled pilot holes. See Figure 6.

FIGURE 3: Coil Flange

FIGURE 4: Horizontal Right Application

FIGURE 5: Horizontal Left Application

ALTERNATE
FLANGE LOCATION
(Used for downflow or
horizontal left installations)

FACTORY

FLANGE

LOCATION

(Used for upflow

or horizontal

right installations)

Furnace

Mounting Plate

Furnace

Mounting Plate

Do not drill any holes or drive any screws into the front duct
flange on the coil in order to prevent damaging coil tubing. See
Figure 6, "PC Series Upflow Coil Installation"

FIGURE 6: PC Series Upflow Coil Installation

Table 2: Coil Projection Dimensions - PC Series Coils

COIL SIZE

DIMENSION “C” INCH

PC18

3-1/2

PC24

4-1/2

PC30, PC32, PC35

4-1/2

PC42, PC43, PC36, PC37

5-1/2

PC48

6-1/2

PC60

9

FIGURE 7: Horizontal Left or Right application (Right Shown)

Flexible
Duct Collar

Do not drill
or Screw
this flange

Field
Fabricated
Ductwork

Upflow
Coil

Upflow
Furnace

Secondary

Drain

Primary

Drain

D

C

(Min)

Alternate

Drain Location

Use tie plate
supplied with coil

Air flow

Gas Furnace