23

Troubleshooting

Trouble

Cause

Remedy

Wrong Rotation (Motor)

Wrong sequence of phases

Switch any two of the three motor leads.

Geareducer Noise

Geareducer bearings

If new, see if noise disappears after one week of operation.
Drain, flush, and refill Geareducer. See Geareducer Service
Manual. If still noisy, replace.

Gears

Correct tooth engagement. Replace badly worn gears.
Replace gears with imperfect tooth spacing or form.

Unusual Fan Drive
Vibration

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment
and supports.

Unbalanced drive shaft or worn
couplings

Make sure motor and Geareducer shafts are in proper
alignment and "match marks" properly matched. Repair or
replace worn couplings. Rebalance drive shaft by adding or
removing weights from balancing cap screws. See Drive
Shaft Service Manual.

Fan

Make certain all blades are as far from center of fan as safety
devices permit. All blades must be pitched the same. See
Fan Service Manual. Clean off deposit build-up on blades.

Worn Geareducer bearings

Check fan and pinion shaft endplay. Replace bearings as
necessary.

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates,
rebalance rotor.

Bent Geareducer shaft

Check fan and pinion shaft with dial indicator. Replace if
necessary.

Fan Noise

Loose fan hub cover

Tighten hub cover fasteners.

Blade rubbing inside of fan cylinder

Adjust cylinder to provide blade tip clearance.

Loose bolts in blade clamps

Check and tighten if necessary.