System Sensor SOUNDER BASE B501BH User Manual

Page 3

Advertising
background image

D650-03-00

3

I56-0491-007R

Figure 4. Wiring diagram:
Detector Activates Sounder Base(s) - (Complies with UL268)
UL has approved grouping for up to six B501BH bases with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BH units in the group to sound. This type of “local” group-

INTELLIGENT

MONITOR

MODULE

(+) 2

(–) 1 6

7

U.L.

LISTED

EOL

RESISTOR

47K

U.L.

LISTED

EOL

RELAY

24V

5

4

1

2

3

5

4

1

2

3

5

4

1

2

3

(+) COMM.

(–) COMM.

(–) POWER

(+) POWER

U.L. LISTED COMP

AT

IBLE

CONTROL

P

ANEL

EXTERNAL 24V SUPPL

Y

CLASS A OPTIONAL WIRING

CLASS A OPTIONAL WIRING

*

GROUPING OF UP TO 6 MODEL B501BH SOUNDER BASES.

OPTIONAL SOUNDER INTERCONNECT

*

ing is accomplished by wiring the grouped devices together
using terminal 5, Sounder Base Interconnect, as shown in
the diagram.
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation system.
It is not acceptable to group horns for primary alarm signaling.

C0971-00

UL LISTED

COMPATIBLE

CONTROL

PANEL

INTELLIGENT

MONITOR

MODULE

INTELLIGENT

RELAY

MODULE

FIRST

SOUNDER

BASE

(+) POWER

(–) POWER

LAST

SOUNDER

BASE

(–) COMM.

(+) COMM.

UL

LISTED

EOL

RELAY

24V

UL LISTED

EOL

RESISTOR

47k

UL LISTED

24V SUPPLY

SLC

(+)

(–)

THIS IS A STANDARD RELAY

MODULE CONFIGURED TO

REVERSE THE POWER

OPTIONAL SOUNDER INTERCONNECT

*

*

GROUPING OF UP TO 6 MODEL B501BH SOUNDER BASES.

C0972-00

Figure 5. Wiring diagram:
Detector Activates Sounder Base(s); Intelligent Relay Module Ac-
tivates All Sounder Bases - (Complies with UL 268 and UL 464)
UL has approved grouping of up to six B501BH bases with horn
units. When wired as a group, any detector in the group that
has its LED’s latched on by the panel will cause other B501BH
units in the group to sound. This type of “local” grouping is

accomplished by wiring the grouped devices together using ter-
minal 5, Sounder Base Interconnect, as shown in the diagram.
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation sys-
tem. It is not acceptable to group horns for primary alarm
signaling.