Technical data of CPU 31xC
6.3 CPU 313C
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
6-11
Technical data
Process diagnostics messages
Yes
•
Simultaneously enabled interrupt S blocks
Max. 20
Testing and commissioning functions
Status/control variables
Yes
•
Variables
Inputs, outputs, memory bits, DBs, timers,
counters
•
Number of variables
–
of those as status variable
–
of those as control variable
Max. 30
Max. 30
Max. 14
Forcing
Yes
•
Variables
Inputs, outputs
•
Number of variables
Max. 10
Block status
Yes
Single step
Yes
Breakpoints
2
Diagnostic buffer
Yes
•
Number of entries (not configurable)
Max. 100
Communication functions
PG/OP communication
Yes
Global data communication
Yes
•
Number of GD circuits
4
•
Number of GD packets
–
Sending stations
–
Receiving stations
Max. 4
Max. 4
Max. 4
•
Length of GD packets
–
Consistent data
max. 22 bytes
22 bytes
S7 basic communication
Yes
•
User data per request
–
Consistent data
max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)
S7 communication
•
As server
Yes
•
as client
Yes (via CP and loadable FBs)
•
User data per request
–
Consistent data
max. 180 bytes (with PUT/GET)
64 bytes
S5-compatible communication
Yes (via CP and loadable FCs)
Number of connections
Max. 8