Schneider Electric MGE GALAXY 5000 User Manual

Page 9

Advertising
background image

ƒ

Bypass voltage

ƒ

Bypass input frequency

ƒ

UPS output voltage (Ph-Ph and Ph-N)

ƒ

UPS output current per phase

ƒ

UPS output frequency

ƒ

UPS output % load

ƒ

UPS output kVA

ƒ

UPS output power factor

ƒ

Battery voltage

ƒ

Crest factor

ƒ

Battery current

ƒ

Battery backup time and remaining service life

Status Indications and Events:

ƒ

Load on battery

ƒ

Load on UPS

ƒ

Load on automatic bypass

ƒ

Low-battery warning

ƒ

General alarm

ƒ

Battery fault

ƒ

Remaining back-up time during operation on battery power

ƒ

Bypass source outside tolerances

ƒ

Additional indications shall provide maintenance assistance



Time-Stamped Historical Events: This function shall time-stamp and store all important
status changes, anomalies and faults and make this information available for automatic or
user-requested consultation.



B. LED Status Indicators: The UPS control panel shall provide three LEDs that signal the

following status conditions:

ƒ

Green LED: Load protected

ƒ

Yellow LED: minor fault

ƒ

Red LED: major fault, load not protected


C. On/Off Switch: The UPS shall provide the ON and OFF buttons to start and stop the

inverter. The switch shall provide a built-in time delay to eliminate the risk of inadvertent
operation (additional confirmation is requested). It is possible to remotely activate the OFF
function via an isolated dry contact to create an emergency power off function, resulting in:

ƒ

Inverter shutdown

ƒ

Opening of the automatic bypass

ƒ

Opening of the input, bypass, output and battery switches/circuit breakers

ƒ

Opening of the isolated dry contact on the programmable relay card

APC – MGE Galaxy 5000 Specification (60Hz)

9

Effective: June 1, 2008 REV X0 JJG

Parallel Module

Advertising