English

5. SYSTEM PARAMETERS

Parameter

Function

Range

[Default]

Description / Notes

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

24

P022

•

Maximum analogue frequency
(Hz)

0 - 400.00

[50.00]

Frequency corresponding to the highest analogue input value, i.e.
10 V, determined by P023. This can be set to a lower value than P021
to give an inverse relationship between analogue input and frequency
output.

i.e.

Note:

The output frequency is limited by values entered for
P012/P013.

P023

•

Analogue input function

0 - 2

[0]

0 = 0 V to 10 V
1 = 2 V to 10 V
2 = 2 V* to 10 V

* The inverter will come to a controlled stop if V < 1 V.

WARNING: The motor can automatically run without a

potentiometer or voltage source connected between
pins 3 and 4.

WARNING: With P023=2, the inverter will automatically start

when V goes above 1 V. This equally applies to
analogue and digital control (i.e. P006 = 0 or 1).

P024

•

Analogue setpoint addition

0 - 2

[0]

If the inverter is not in analogue mode (P006 = 0 or 2), setting this
parameter to ‘1’ causes the analogue input value to be added.

0 = No addition.
1 = Addition of the analogue setpoint (defined by P023) to the

fixed frequency or the motor potentiometer frequency.

2 = Scaling of digital/fixed setpoint by analogue input (P023) in

the range 0 - 100%.

Note:

By selecting a combination of reversed negative fixed
frequency settings and analogue setpoint addition, it is
possible to configure the inverter for ‘centre zero’ operation
with a +/-5 V supply or a 0 - 10 V potentiometer so that the
output frequency can be 0 Hz at any position, including the
centre position.

P027

•

Skip frequency 2 (Hz)

0 - 400.00

[0.00]

See P014.

P028

•

Skip frequency 3 (Hz)

0 - 400.00

[0.00]

See P014.

P029

•

Skip frequency 4 (Hz)

0 - 400.00

[0.00]

See P014.

P031

•

Jog frequency right (Hz)

0 - 400.00

[5.00]

Jogging is used to advance the motor by small amounts. It is controlled
via the JOG button or with a non-latching switch on one of the digital
inputs (P051 to P053).

If jog right is enabled (DINn = 7), this parameter controls the frequency
at which the inverter will run when the switch is closed. Unlike other
setpoints, it can be set lower than the minimum frequency.

P032

•

Jog frequency left (Hz)

0 - 400.00

[5.00]

If jog left is enabled (DINn = 8), this parameter controls the frequency
at which the inverter will run when the switch is closed. Unlike other
setpoints, it can be set lower than the minimum frequency.

f

V

P021

P021

P022

P022