Configuring the query, With a generic modbus slave, Configuring the gateway – Schneider Electric Gateway LUFP7 User Manual

Page 71

Advertising
background image

72

6. Configuring the Gateway

Name of the Modbus slave

Name of the Modbus command

Modbus query

! Frame "

Slave no.
Function no.
Word no. (MSB / LSB)
Value of the word (MSB / LSB)
CRC16 (LSB / MSB)

Modbus response

! Frame "

Slave no.
Function no.
Word no. (MSB / LSB)
Value of the word (MSB / LSB)
CRC16 (LSB / MSB)

These elements can be configured using AbcConf. There is a description of them in the following chapters. We
will then return to the example of the ATS48 to illustrate how to use these elements.

6.11.2.1. Managing degraded modes

Due to the number of hardware elements and software tools used, the following table shows a summary of the
various degraded modes in a Profibus-DP application. This description only applies to a Premium PLC fitted with
a TSX PBY 100 coupler:

Event

Desired

behaviour

Premium PLC:

CPU stop/failure

(1)

Disconnection

of the upstream

Profibus-DP

network (2)

Failure of the

LUFP7 gateway

(3)

Disconnection of

the downstream

Modbus RTU

network (2) (3)

Reset

“Outputs” option
equal to “Reset”

“Offline options for

fieldbus” = “Clear”

Hold

“Outputs” option

equal to “Hold”

“Offline options for

fieldbus” = “Freeze”

Depending on the configuration

of the Modbus slaves

Outputs

No refresh

——

“Offline options for

fieldbus” = “No Scanning”

——

Reset

——

Always

“Offline options for sub-

network” = “Clear”

Inputs

Hold

——

——

“Offline options for sub-

network” = “Freeze”

(1) The “Outputs” option is described in chapter 4.2.8 Importing the Configuration of the Profibus-DP Network

under PL7 PRO, page 31. Under PL7 PRO, it can be accessed from the configuration screen for the
TSX PBY 100 board.

(2) The “Offline options for fieldbus” and “Offline options for sub-network” are described in the next chapter.
(3) The behaviour desired with regard to the outputs should be directly configured on each of the Modbus

slaves. In the case of drives marketed by Schneider Electric, for instance, resetting the outputs is
configured by setting the NTO bit to 0 (communication control), and they are held by setting NTO to 1
(suppression of communication control).

You may also refer to chapter 4.2 Degraded application mode of the Implementation manual – TSX PBY 100 –
PROFIBUS-DP

(ref.: TSX DM PBY 100E) for further details regarding the processing of degraded modes by the

TSX PBY 100 board.