Siemens SIMATIC PC Adapter TS Adapter User Manual

Page 19

Advertising
background image

PC/TS Adapter

Quick Reference Guide

PC/TS Adapter
A5E00078070-02

15

The switch is operated only infrequently and is recessed so
that it cannot be operated inadvertently. See Figure 1-11 for
the location of the switch. Both switch positions are labeled
on the underside of the unit.

To operate the switch, please use a ball-point pen
(“retractable ball-point”) up to a diameter of 1.7 mm or a blunt
instrument of the same size. Insert the extended point
between the operating lever and the housing cutout on the
side with the operating lever, and slide the operating lever
into the opposite position (see Figure 1-11).

!

Warning

Pointed objects (for example, needles) or
breakable objects (for example, pencils) must not
be used for operating the switch.

6.6

Function of the Power LED

LED

Meaning

Response

Off

S

24 V DC supply
voltage missing

S

Fatal hardware fault

Check voltage
supply

Replace adapter

Constant
blinking

Hardware fault
detected per software

Replace adapter

On

Ready for use*

* After switching on, a few seconds will elapse before the

LED lights up

.

6.7

Function of the active LED

The active LED shows that the adapter on the MII/DP bus is
transmitting.

Advertising