9.6 Unitelway/Modbus serial cable

This 2m cable can be delivered as accessory to connect Schneider PLCs; It has a SUBD9 connector at the eWON®
side and a MiniDIN connector at the PLC side.

D(A) is connected to B- and D(B) is connected to A+

MiniDIN PIN

Schneider Signal

Name

eWON® Signal Name

eWON® SUBDB9

connector

1

D(B)

A+

DB9 pin 3: A+

2

D(A)

B-

DB9 pin 8: B-

3

4

5

6

7

GND

GND

DB9 pin 5: GND

8

Connector shield

Table 29: MiniDin and SubDB9 connectors pinout