System Sensor DH200RPL User Manual

Page 6

Advertising
background image

D200-39-00 6 I56-1977-004R

Figure 10. Wiring Diagram for DH200RPL Duct
Detector with optional RA400Z:

5 7

RA400Z

5 = Alarm Signal
7 = Aux. Power (–)

DO NOT BREAK TAB ON RA400Z

Figure 11. System Wiring Diagram for DH200RPL
Duct Smoke Detector with RTS451/RTS451KEY:

ALARM SIGNAL

AUX. POWER (–)

TEST +

TEST –

ALARM SIGNAL

NOT USED

NOT USED

CIRCUIT

REFERENCE

TEST

SWITCH

FOR RTS451, TERMINAL 3 IS NOT

USED. (RTS451 DOES NOT HAVE

A TERMINAL 6.) FOR RTS451KEY,

TERMINALS 3 AND 6 ARE NOT USED.

RTS 451/RTS451KEY

5

7

4

3

1

3

6

2

4

5

5 7

PA400

5 = Alarm Signal
7 = Aux. Power (–)

Figure 12. Wiring Diagram for DH200RPL with
optional PA400:

[9.2] Standby, Alarm, And Sensitivity Tests
[9.2.1] Standby And Trouble
Standby — If the system control panel is programmed, look for the
presence of the flashing LEDs through the transparent
housing cover. The LED will flash with each communicat-
ion.

Trouble — If the detector LEDs do not flash, then the de-tector lacks
power (check wiring, panel pro-gramming, or power sup
ply), the detector board is missing (replace), or the unit
is defec-tive (return for repair). Additionally, if the cover
is removed for more than 20 minutes, the LEDs of the
detector will not flash.

Test — The trouble condition can be caused intentionally to veri-
fy correct operation of the system. Remove the detector
board to cause a trouble condition locally and at the sys-
tem control panel.

[9.2.2] Alarm Tests
[9.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST locator on the

bottom of the detector housing (Figure 13).

2. Verify system control panel alarm status and control panel execution

of all intended auxiliary functions (i.e. fan shutdown, damper control,
etc.)

3. The detector is self-restoring when the magnet is removed. Verify that

the system control panel has reset; panel may have to be reset.

Figure 13. Testing detector alarm:

Figure 14. Insulator Card for DH200RPL Duct Smoke
Detector: