System Sensor 4WT-B User Manual

Page 3

Advertising
background image

D100-96-00 3

I56-1800-08R

2-Wire i3 Detector Wired in Style D Configuration:

CAUTION

Any 2-wire i

3

smoke detector (2W-B, 2WT-B, 2WTA-B, or 2WTR-B)

wired in the Style D initiating device circuit (IDC) configuration
requires the use of a 2W-MOD2 module. This is because fire
alarm control panels vary by manufacturer on the implementa-
tion of Style D circuits. Therefore, the only way to insure proper
operation of 2-wire i

3

smoke detectors (2W-B, 2WT-B, 2WTA-B, or

2WTR-B) on Style D IDC’s is to use a 2W-MOD2 module. Refer
to the 2W-MOD2 installation manual, document D500-46-00,
for Style D wiring diagrams. The 2W-MOD2 installation
manual may be downloaded from the System Sensor web site
at www.systemsensor.com.

Installation

WARNING

Remove power from alarm control unit or initiating device circuits
before installing detectors.

NOTE: To install units so that corresponding LEDs are lined up,
refer to the “Green LED” indicator on the base.
1. Wire the mounting base screw terminals per Figure 3a or

Figure 3b, as applicable.

2. Place detector on the base and rotate clockwise. The detector

will drop into the base and lock into place with a “click”.

3. After all detectors have been installed, apply power to the

alarm control unit.

4. Test each detector as described in Testing.
5. Reset all the detectors at the alarm control unit.
6. Notify the proper authorities that the system is in operation.

CAUTION

Dust covers are an effective way to limit the entry of dust into
the smoke detector sensing chamber. However, they may not
completely prevent airborne dust particles from entering the detec-
tor. Therefore, System Sensor recommends the removal of detectors
before beginning construction or other dust producing activity. When
returning the system to service, be sure to remove the dust covers
from any detectors that were left in place during construction.

Testing

Detectors must be tested after installation and following
maintenance.

NOTE: Before testing, notify the proper authorities that mainte-
nance is being performed and the system will be temporarily out
of service. Disable the zone or system undergoing maintenance to
prevent any unwanted alarms.

Ensure proper wiring and power is applied. After power up, allow
80 seconds for the detector to stabilize before testing.

Test i

3

Series detectors as follows:

A. Test Switch

1. An opening for the recessed test switch is located on the

detector housing (See Figure 5).

2. Insert a small screwdriver or allen wrench (0.18

w max.) into

the test switch opening; push and hold.

3. If the detector is within the listed sensitivity limits, the

detector’s red LED should light within five seconds.

Figure 5: Recessed Test Switch Opening and SENS-RDR

Position

PUSH RECESSED
SWITCH WITH A
0.18

w MAX.

DIAMETER TOOL

LED

RECESSED TEST SWITCH

POSITION SENS-RDR
AT AN ANGLE ON THE
OVAL AREA OR AT THE
CHAMBER OPENING
BY THE WORD “PAINT”

S0135-00

B. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the

detector and gently blow the smoke through the detector until
it alarms.

C. Direct Heat Method (models 2WT-B and 4WT-B only)
Using a 1000-1500 watt hair dryer, direct the heat toward either

of the thermistors. Hold the heat source about 12 inches from
the detector to avoid damage to the plastic.

NOTE: For the above tests, the detector will reset only after the
power source has been momentarily interrupted.

If a detector fails any of the above test methods, its wiring should be
checked and it should be cleaned as outlined in the Maintenance
section. If the detector still fails, it should be replaced.

Notify the proper authorities when the system is back in service.

Loop Verification (models 2W-B and 2WT-B only)

Loop verification is provided by the EZ Walk loop test feature.
This feature is for use with i

3

Series compatible control panels or

the i

3

Series 2W-MOD module only. The EZ Walk loop test verifies

the initiating loop wiring and provides visual status indication at
each detector.

1. Ensure proper wiring and power is applied. Wait approxi-

mately six minutes before performing EZ Walk test.

2. Place control panel or module in EZ Walk Test mode (refer

to panel manufacturer’s manual or 2W-MOD manual D500-
46-00).

3. Observe the LEDs on each detector:

Table 3: EZ Walk Test Detector Modes

Green LED

Red LED

Proper Operation

Double blink 5 sec

Out of Sensitivity

Double Blink 5 sec

Freeze Condition

Double Blink 10 sec

NOTE: The EZ Walk loop test must not be used instead of alarm

testing.

Maintenance

NOTE: Before performing maintenance on the detector, notify
the proper authorities that maintenance is being performed and
the system will be temporarily out of service. Disable the zone or
system undergoing maintenance to prevent any unwanted alarms.
Power must be removed from the detector before performing
maintenance of any kind.

Advertising
This manual is related to the following products: