1. Burner orifi ce too small.

1.

Irregular orifi ce causing whistle or resonance.

2. Excessive gas input.

1. Clogged main burners.
2.

Misaligned

orifi

ces.

3. Insuffi cient combustion air.
4. Possibly over fi red.

1.

Blocked

venting.

2. Insuffi cient combustion air.
3. Blocked heat exchanger.
4. Air leak into combustion chamber

or draft hood.

1.

Shut off gas supply immediately!

2. Leaking gas test port on valve.
3. Blocked heat exchanger.
4. Blocked draft hood.
5. Negative pressure in the building.

1.

Improper

ground.

2. Bad or broken spark cable.
3.

Faulty

control.

4. Pressure regulator set too low.

5. Main burner orifi ces dirty.
6.

Improper

venting.

1. Gas supply is off.
2. No power supply to unit.

3. Thermostat not calling.

4. Defective high limit.

5. Defective drafter prove switch.

6.

Loose

wiring.

7.

Improper

ground.

8. Improper thermostat or transformer wiring.

1.

Improper

venting.

2. Unit under fi red.

3. Building too cold.

Table 6 - Tubular Propeller Troubleshooting Guide

1.

Check with local gas supplier for proper orifi ce
size and replace. Refer to “Operation”.

1.

Replace

orifi

ce.

2. Test and reset manifold pressure.

1. Clean main burner ports.
2. Replace manifold assembly.
3. Insuffi cient combustion air.
4. Check gas input and manifold pressures.

1. Clean Flue. Refer to “Installation”.
2. Clean combustion air inlet openings.
3. Clean heat exchanger. Refer to “Installation”.
4. Determine cause and repair accordingly.

1. Inspect all gas piping and repair.
2. Check to ensure gas test ports are seated.
3. Clean heat exchanger/fl ue.
4. Clean fl ue collector.
5.

See

“Installation”.

1. Check grounding wires and spark bracket

connections.

2. Inspect spark cable connections and cuts.
3. Check to ensure spark is energized after

pre purge period.

4. Test and reset manifold pressure refer to

“Operations”.

5. Clean or replace orifi ces.
6.

Refer

to

“Installation”.

1. Open all manual valves “check for leaks”.
2. Turn on power supply, check fuses and

replace if bad.

3. Turn up thermostat, Check for 24v on

terminals R and W1 on terminal strip.

4. Check switch for continuity if open with no

heat present, replace.

5. Check switch operation to ensure

switch closes after draftor purge period.
If it does not make/check tubing
connections/ blockage.

6. Check all wiring per diagram.
7. Check all ground wires and connections.
8. Check both, for wiring according to diagram;

check for 24V at gas valve terminals during

trial for ignition period if present and valve
does not open. Replace valve.

1.

Refer

to

“Installation,

Venting”.

2. Check gas supply pressures to unit. Refer

to “Installation”.

3.

Refer

to

“Installation”.

A. Flame pops back.

B.

Noisy

Flame.

C. Yellow tip fl ame (some yellow

tipping on LP gas is permissible).

D.

Floating

fl

ame.


E.

Gas

odor.

F.

Delayed

ignition.

G. Failure to ignite.

H.

Condensation.

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION