D400-07-00 3 I56-279-05R

CAUTION

Dust covers can be used to help limit dust entry to the
detector, but they are not a substitute for removing the
detector during building construction. Remove any dust
covers before placing system in service.

CAUTION

Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found
suitable for that purpose.

Testing
Before testing the detector, look for the presence of the
flashing LED. If it does not flash, power has been lost to the
detector (check the wiring), or it is defective (return for
repair – refer to Warranty).

Detectors must be tested after installation and following
periodic maintenance. Notify the proper authorities that
the system is undergoing testing. The 1400 may be tested
as follows:

A. Recessed Test Switch
1. A test switch is located on the detector housing (See

Figure 4).

2. Push and hold the recessed test switch with a 0.1 inch

maximum diameter tool.

3. The LED on the detector should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R)
The MOD400R is used with an analog or digital voltme-

ter to check the detector sensitivity as described in the
test module manual.

C. Aerosol Generator (Gemini 501)
Set the generator to represent 4%/ft. to 5%/ft. obscuration

as described in the Gemini 501 manual. Using the bowl
shaped applicator, apply aerosol until the unit alarms.

Notify the proper authorities that the system is back on
line.

Detectors that fail these tests should be cleaned as described
under MAINTENANCE and retested. If the detectors still
fail these tests, they should be returned for repair.

+

REMOTE

ANNUNCIATOR

+

+

REMOTE

ANNUNCIATOR

CLASS A OPTIONAL WIRING

NOTE: IF REMOTE ANNUNCIATOR IS NOT USED, POLARITY TO DETECTOR MAY BE REVERSED.

EOL

RESISTOR

INITIATING

LOOP

UL LISTED

COMPATIBLE

CONTROL

PANEL

+

+

3

2

1

3

2

1

Figure 3. Wiring diagram for 1400 smoke detector used with two-wire control panel:

S0141-00

PUSH RECESSED TEST SWITCH WITH

A 0.1" MAX. DIAMETER TOOL.

TEST MODULE

SOCKET

LED

RECESSED

TEST SWITCH

TAMPER SLOT

Figure 4. Bottom and side views showing position of test switch: