Wiring – Siemens OpenAir GND Series User Manual

Page 5

Advertising
background image

OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers

Technical Instructions

Document No. 155-746

March 17, 2005

Wiring

All wiring must conform to NEC and local codes and regulations.

Function Color

Supply Red

Neutral Black

Ground Green

Wire Designations

24 Vac/dc

M

BLACK

(NEUTRAL)

RED

(SUPPLY)

GREEN

(GROUND)

EA0941R1

Figure 2.

Function Color

Line Black

Neutral White

Ground Green

120 Vac

M

WHITE

(Neutral)

BLACK (Line)

GREEN

(Ground)

EA1167R2

Figure 3.

Function

Color

Line Brown

Neutral Blue

Ground Green

230 Vac

M

BLUE

(Neutral)

BROWN (Line)

GREEN

(Ground)

EA0609R2

Figure 4.

CAUTION:
The actuator must be wired
with a 230 Vac line with respect
to neutral and the ground lead
must be connected for proper
protection of the actuator. Any
other connection, such as
phase-to-phase, can damage
the actuator.

Auxiliary Switches

YELLOW

GRAY

85∞

5∞

EA1163R2

Figure 5.

Switch

Wire

Color

Switch

Makes

Switch

Breaks

Gray

< 5°

> 5°

85°

Yellow > 85°

< 85°


NOTE:
Both sets of contacts are open when actuator is
between 5° and 85°.

Siemens Building Technologies, Inc.

Page 5 of 7

Advertising