3.5 Design

SIMATIC IPC427C

18

Operating Instructions, 04/2009, A5E02414743-01

3.5.2

Connection components

Ports and power supply

Location of connection elements (version with PROFIBUS or CAN)



















Pos Name

Description

①

24 VDC

Connection for a 24 V DC power supply

②

DVI/VGA

DVI/VGA connection for CRT or LCD monitor with DVI interface

③

USB

4 USB 2.0 connections, high-speed / low current

④

PN/IND. ETHERNET RJ45 Ethernet connection 1 (exclusive PCI interrupt) for 10/100/1000 Mbps

⑤

PN/IND. ETHERNET RJ45 Ethernet connection 2 (shared PCI interrupt) for 10/100/1000 Mbps
PROFIBUS DP/MPI

⑥

CAN fieldbus

PROFIBUS DP/MPI interface (RS 485 isolated), 9-pin Cannon socket or CAN fieldbus

(on request)

⑦

COM1

Serial port (RS232) 9-pin Cannon connector

⑧

USB strain-relief

fastener

The USB strain relief must be fastened to the device enclosure with an oval-head screw

(M4 thread). The USB cables can be fastened to the strain-relief assembly with a cable

tie.

⑨

PE terminal

The PE terminal (M4 thread) must be connected to the protective ground conductor of the

plant, in which the device is to be installed. The minimum conductor cross-section may not

be less than 2,5 mm

2

.

Location of the connection elements (second COM interface)



Pos Designation

Description

①

COM2

Serial port (RS232) 9-pin Cannon connector