5 controller setpoints – Sterling GP Series User Manual
Page 28
 
GP Series Portable Chillers
Chapter 4: Operation
28 of 44
4-5 Controller
Setpoints
Access Level
Variable Description
Operator Supervisor
Leaving Temp
Temperature of fluid out to process
x
x
Hi Temp Warning
Setpoint for alarm to warn when leaving fluid 
temperature is too high 
x x
Hi Temp Fault
Setpoint to shut down pump and compressor based on 
leaving fluid temperature 
x x
Compressor On 
Differential 
Temperature Difference between Leaving Fluid 
Temperature and Setpoint to turn on the compressor 
x
Compressor Off 
Differential 
Temperature Difference between Leaving Fluid 
Temperature and Setpoint to turn off the compressor 
x
Pump Stop Delay
Delay time in seconds between fault and stopping the 
pump 
x
Low Temperature 
Warning 
Temperature to activate Low Temperature Warning 
alarm 
x
Low Temperature Fault
Temperature to activate Low Temperature Fault alarm
x
Water Make-up On
The tank level to turn on optional water make-up valve; 
based on size of tank 
x
Water Make-up Off
The tank level to turn off optional water make-up valve; 
based on size of tank. 
x
Water Make-up Time
The time in seconds that controller will allow for filling 
the tank 
x
Low Level Warning
Tank level that will activate Low Level Warning alarm
x
Low Level Fault
Tank level that will activate Low Level Warning fault
x
High Level Warning
Tank level that will activate High Level Warning alarm
x
High Level Fault
Tank level that will activate High Level Warning fault
x
High Temperature 
Delay 
Delay time in minutes between fault and stopping the 
compressor and pump 
x
Alarm Silence Time
Time in minutes to silence alarm (with optional audible 
alarm). After time alarm will reactivate. 
x
Operator Password 
Time 
Time in minutes for operator password to be active
x
Supervisor Password 
Time 
Time in minutes for supervisor password to be active
x