Basin heaters systems will not prevent the coil from freezing.

Unless some means of freeze prevention is incorporated into your
system, the tower basin and exposed pipework should be drained at
the beginning of each wintertime shutdown period.

If fluid cooler basin is drained, verify that all basin heaters have been
shut off either by automatic cutoff or disconnect switch.

Protection against Coil Freezing:

Ethylene and propylene glycol solutions are the best means to protect the
coil from freezing. The following table provides the coil volume for each
MC Fluid Cooler model. When the use of industrial antifreeze solutions is
not possible, the system must be operated to meet both of the following
conditions.

1. Maintain sufficient flow rate through the coil.

2. Maintain sufficient heat load on the process fluid. Fluid exiting the

coil must be maintained at or above 45°F. Cycling of the recirculation
pump should not be used to control process temperatures.

Draining the coil is not acceptable as a normal method of freeze
protection—draining promotes corrosion inside the coil tubes. Drain-
ing is acceptable in an emergency if the coil is not protected by an
antifreeze solution.

It is recommended that you discuss your freeze prevention options with
your local Marley sales representative.

Operation

Warning

Model

Coil Volume

US Gallons

Model

Coil Volume

US Gallons

MCF7012_081

11

MCF7055_081

70

MCF7012_101

13

MCF7055_101

88

MCF7012_121

16

MCF7055_121

106

MCF7013_081

17

MCF7073_081

43

MCF7013_101

21

MCF7073_101

54

MCF7013_121

25

MCF7073_121

65

MCF7014_081

23

MCF7074_081

61

MCF7014_101

28

MCF7074_101

76

MCF7014_121

34

MCF7074_121

91

MCF7054_081

46

MCF7075_081

89

MCF7054_101

58

MCF7075_101

112

MCF7054_121

69

MCF7075_121

134