P910, P918, P922 – Siemens Stober CombiDrive CM400/3 User Manual

Page 29: P923, P931, P944

Advertising
background image

4. Clear Text Display Module & System Parameters

English

© STÖBER plc 1997

27

05.02.01

Parameter Function

Range

[Default]

Description / Notes

P910

••••

Local/Remote mode

0 - 4

[0]

Sets the inverter for local control or remote control over the serial link:

0 = Local control

1 = Remote control (and setting of parameter values)

2 = Local control (but remote control of frequency)

3 = Remote control (but local control of frequency)

4 = Local control (but remote read and write access to

parameters and facility to reset trips)

Note:

When operating the inverter via remote control (P910 = 1
or 3), the analogue input remains active when P006 = 1
and is added to the setpoint.

P918

••••

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details

.

(Access only possible with P099 = 1.)

P922

Software version

0.00 -
99.99

[-]

Contains the software version number and cannot be changed.

P923

••••

Equipment system number

0 - 255

[0]

You can use this parameter to allocate a unique reference number to
the inverter. It has no operational effect.

P927

••••

P928

••••

P930

Most recent fault code

0 - 9999

[-]

The last recorded fault code (see section 5) is stored in this
parameter. It is cleared when the inverter is reset.

P931

Most recent warning type

0 - 9999

[-]

The last recorded warning is stored in this parameter until power is
removed from the inverter:

002 = Current limit active
003 = Voltage limit active
005 = Inverter over temperature (internal PTC)

P944

Reset to factory default settings

0 - 1

[0]

Set to ‘1’ and then press P to reset all parameters except P101 to the
factory default settings.

P947
P958
P963
P967
P968
P970
P971

••••

EEPROM storage control

0 - 1

[1]

0 = Changes to parameter settings (including P971) are lost when

power is removed.

1 = Changes to parameter settings are retained during periods

when power is removed.

IMPORTANT
Take care not to exceed the EEPROM write cycle limit of
50,000/parameter (approx.) when using the serial link to update
parameters, otherwise data loss or corruption may occur. Read cycles
are unlimited.

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Access only possible with P099 = 1.)

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Cannot be accessed unless P099 = 1.)