this displays the output voltage and current of the

battery you are charging. ( a less current but higher voltage )

( this is the setup information screen ) This screen gives different

information depending on the system cycle, it is informing you., WET OPEN= wet open lead acid cell batteries,
this shows that the system battery type dip switches are set for wet cell batteries,( 14.8 v max setting ) Bulk
charge refers to the initial charge rate, this could change to a timer, then adventually change to float ( float
charger 14 volts )

This screen shows the time left to the next pause cycle

( for 2.5 min. ) and that it is on auto. The auto can be removed by pushing buttons 1 and 2 together. This
removes the auto pause control, and the charger will still have all its safety and timing cycles, every 20 min.
pause

R:v2.0 C:v2.0, this shows the software version for

remote ( R ) and for main PCB ( C ). the 12vIN-12vOUT, refers to the motel, a 12v-12v unit. There are 12-24 v,
24-24 and 24-12.

: There are 2 x screens on this button. Push once for screen a, then

again for screen b. Screen a shows the alternator temp and the domestic battery temp, if the temperature
sensors are not fitted it will default to 20 deg C

Temp 4a+b: There are 2 x screens on this button. Push once

for screen a, then again for screen b. Screen b shows the box heat sink temperatures, LHS stands for left hand
side, Guess what RHS stands for.
Do not expect these to be the same temperature

Pre set voltages:
Minimum input voltage the unit will run at 13 volts
Voltage the unit switches off and drops into sleep mode
below 12.8 v for at lease 15 mins
Power consumption on sleep mode. 5 ma ie 0.005 amps
max input voltage trip 15.5
max output voltage trip 15.5

Alt temp disengage 100 deg C
Reset alt 80
Battery temp trip 50 deg C
Heat sink trip 70 deg C
Heat sink reset 60 deg C
Fans on at 50 deg C
Fans on over 35 amps
Fans of at 45 deg C
Low battery alarm 1 2.5 v
Low battery regulation 13 v
high battery voltage trip 15.5v
Max input current at 12 v = 45 amps
amp meter +/- about 10%
voltmeter +/- 1%

Push button marked 2 again: screen E/b

Screen F/a: Push button marked 3

Push button marked 3 again: screen F/b.

Push button marked 3 again: screen F/c.

Screen G/a: Push button marked 4.

Screen G/b:: Push button marked

( x 2 for 24 v models )

All voltages refer to a default temperature of 20 deg c

if the battery temperature sensor is fitted these voltages will be less depending on

the battery temperature