System Sensor FTX-P1 User Manual

Page 3

Advertising
background image

D200-72-00

3

I56-1184-04R

TEST MAGNET
MARKER

Cover is keyed to
fit into 4 matching
size slots.

4 5

6

3

7

8

2

1

9

0

4 5

6

3

7

8

2

1

9

0

A78-2460-00

Figure 2. Rotary decade address switches:

Figure 3. Test magnet position:

Figure 4. Replacing the filter cover:

the detector still fails any test, have its filter replaced (see in-
structions below) and retested. Finally, if the detector contin-
ues to fail after replacing the filter, it must be returned for
repair or replacement.

When testing is complete, restore the system to normal op-
eration and notify the proper authorities that the system is
back in operation.

Cleaning
The unique design of Filtrex eliminates the need for typical
detector cleaning. The only maintenance necessary is re-
placing the filter, which is signaled by a trouble condition
at the panel (see below).

Filtrex has been designed to maximize the amount of time
before maintenance is required. Filtrex utilizes a replaceable
filter that may become clogged over time. Filtrex monitors
itself to insure that the filter has not become clogged. Be-
cause environmental conditions can vary significantly, the
amount of time before maintenance could vary significantly
as well. To fully understand the maintenance requirements
of Filtrex in its installed location, it is recommended that the
following test program be conducted.
1. Install Filtrex in the desired location.
2. Connect Filtrex to the fire alarm control panel.
3. Maintain a record for at least 90 days of any mainte-

nance performed on or required by Filtrex.

4. At the end of the test period, use the record to develop

and schedule maintenance. Filtrex detectors should be
serviced at regular intervals to insure that the fire alarm
system provides continuous protection.

Replacing the Filter
IMPORTANT:

When the filter becomes too clogged to draw ad-
equate air into Filtrex, power is automatically cut
from the detector, sending a trouble signal to the
fire control panel. After 5 minutes, power is re-
stored to the detector for 72 hours. After 72 hours,
power is cut again and the detector will remain off-
line until the filter is replaced.

Note: The unit has two filters. The replaceable filter is in-
side the cover. A permanent filter is mounted to the unit.

1. Grasp the Filtrex housing with one hand and the cover

with the other. Turn the cover counterclockwise fully
(approx. 30 degrees) and remove cover by pulling it
away from detector unit (see Figure 4).

2.Replace with new filter and cover assembly. The cover is

keyed so it fits in place only one way. Turn the cover
clockwise until it stops.
NOTE: The base is equipped with an optional tamperproof
feature which can be used to prevent unintentional removal
of Filtrex while replacing the filter.

Alignment marks are
provided on the cap
and top of the
permanent filter.

Advertising