SITRANS P measuring instruments for pressure

Transmitters for food, pharmaceuticals and biotechnology

SITRANS P Compact
for gage and absolute pressure

2/22

Siemens FI 01 · 2009

2

■

Function

The process pressure acts on a piezo-resistive semiconductor
measuring bridge through a remote seal and a transmission liq-
uid. The pressure transmitter converts the pressure values into a
load-independent current.

A compensation network makes the output signal largely inde-
pendent of the ambient temperature. As a result of a specially
adapted remote seal connection with minimized volume, the in-
fluence of the process temperature on the output signal is
greatly reduced compared to a conventional screw connection.

The pressure transmitters can be powered with a non-regulated
DC voltage of 10 to 30 V. Output signals common to measuring
technology are available.

■

Technical specifications

Pressure transmitters for food, pharmaceuticals and biotechnology

Mode of operation

Measuring principle

Piezo-resistive

Input

Measured variable

Gage or absolute pressure

Measured range

0 ... 160 mbar (0 ... 2.32 psi)
...
0 ... 40 bar (0 ... 580 psi)

Output

Output signal

• Two-wire system

4 ... 20 mA

• Three-wire system

0 ... 20 mA

Measuring accuracy

To EN 60770-1

Linearity error including hysteresis
(reference point adjustment)

≤ 0.2% of full-scale value

Adjustment accuracy

≤ ± 0.2% of full-scale value

Adjustment time

< 20 ms

Influence of ambient temperature

On th enclosure

• Zero

< 0.2%/10 K of full-scale value

• Measured span

< 0.2%/10 K of full-scale value

On the process connection (remote
seal)

Zero error (depends on design)

• Flange remote seal

- DN 25 / 1"

4.8 mbar/10 K (0.070 psi/10 K)

- DN 32 / 1¼”

2.3 mbar/10 K (0.033 psi/10 K)

- DN 40 / 1½”

1.6 mbar/10 K (0.023 psi/10 K)

- DN 50 / 2"

0.6 mbar/10 K (0.009 psi/10 K)

• Clamp-on seal

- DN 25 / 1"

9.5 mbar/10 K (0.138 psi/10 K)

- DN 32 / 1¼”

4.1 mbar/10 K (0.060 psi/10 K)

- DN 40 / 1½”

3.9 mbar/10 K (0.057 psi/10 K)

- DN 50 / 2"

3.9 mbar/10 K (0.057 psi/10 K)

The zero error specified for the process connection should be consid-
ered as a guideline for a standard design. We will produce a detailed
system calculation on request. Systems with reduced remote seal errors
are available on request.

Rated conditions

Installation conditions

• Mounting position

Any, vertical as standard

Ambient conditions

• Ambient temperature

-10 ... +70 °C (14 ... 158 °F)

• Storage temperature

-10 ... +90 °C (14 ... 194 °F)

• Process temperature

Max. 200 °C (392 °F), depends
on design

• Degree of protection (to EN 60529) IP65, optional IP67

• Electromagnetic compatibility

- Emitted interference

To EN 50081 Part 1, issue 1993
(residential and industrial areas).
The unit has no own emissions.

- Interference immunity to

EN 50082 Part 2, issue March
1995 (industrial areas)

Design

Weight (without remote seal)

• Field housing

≈ 460 g (≈ 1.01 lb)

• Housing with plug

≈ 200 g (≈ 0.44 lb)

Housing

• Designs

• Field housing IP65 or IP67, with

screwed gland

• Angled plug DIN 43650, IP65

• Cable connection, IP67

• Round plug connector M12,

IP65

• Material

Stainless steel, mat.
No. 1.4404/1.4305

Material of union nut

Polyamide (with electrical con-
nection using plug or cable)

Electronics unit potted with sili-
cone

Internal ventilation for measuring
ranges < 16 bar (< 232 psi),
through housing thread or con-
nection cable depending on
design

Process connection

• Versions

See Ordering data

• Material of coupling

Stainless steel, mat.
No. 1.4404/316L

Power supply

Terminal voltage on transmitter

10 ... 30 V DC

Rated voltage

24 V DC

Certificate and approvals

Classification according to pressure
equipment directive
(DRGL 97/23/EC)

For gases of fluid group 1 and liq-
uids of fluid group 1; complies
with the requirements of article 3,
paragraph 1 (appendix 1);
assigned to category III, confor-
mity evaluation module H by the
TÜV Nord

Explosion protection

• Intrinsic safety "i"

TÜV 03 ATEX 2099 X

- Identification

Ex II 2G EEx ib IIC T6

© Siemens AG 2008