Smith Cast Iron Boilers GT Series User Manual

Page 27

Advertising
background image

GT INSTALLATION AND OPERATION INSTRUCTIONS

Page 27

Figure 38 - Input Conversion Chart

Setting Sentry 2100T control
Programming is accomplished by a series of three push
buttons located on the bottom side of the control. To
enter the programming mode, press the function key
once, “RUN” should be displayed on the screen. To scroll
through the various menu options depress ↑. To alter the
value of a menu option press “Function” once while the
menu option is displayed, and the current value will be
displayed, then use ↑ for up, and ↓ for down, until the
desired value is obtained. To enter the selected value
press “Function”, which will return to the menu and store
the new setting. When all desired values are set, scroll to
the “RUN” menu option, and press Function, which exits
the Programming Mode and initiates normal operation.
If the control is left in the Program Mode longer than 30
seconds without receiving any input the unit will turn off.
Press “Function” once to continue programming or to
restart boiler operation.

Below is a list of functions and a description of what
they control:
RUN - Stores Values & initiates
LO - Boiler Setpoint for DHW, 80 - 200°F, 27 - 93°C
HI - Boiler Setpoint for Heating, 80 - 200°F, 27 - 93°C
DIF - Differential, 1 - 40°F, -17°C - 4°C
RES - Sets Outdoor Reset Curve Slope,
70°F, 21°C to HI
SFS - Sets Starting Gas Input Value, 60 to 100

GT150 & 200 is 60 to 100
GT-400 is 45 to 90

HFS - Sets Highest Gas Input Value, 100 to 240

GT-150 & 200 is 100 to 240
GT-400 is 90 to 195

LFS - Sets Lowest Gas Input Value, 40 to 100

GT-150 & 200 is 40 to 100 (see note)
GT-400 is 35 to 90

NOTE: LFS must not be set below 48 on the GT150
model. To start the control operation return to
“RUN” on the menu and press “Function”. Normal
operation will begin.

Recommended Settings
When programming the Sentry 2100T determine
what the hottest boiler temperature required for the
coldest day will be. This will be the HI SETTING. If
an indirect tank is used for domestic hot water, DHW,
determine the minimum boiler temperature required
to ensure an adequate supply of hot water. This is the
LO SETTING. The LO SETTING is only used during
a call for DHW, when A and C terminals are closed.
Set the LO to the temperature required for the Indirect
Water Heater. 140 °F, 60°C or at least 30°F, -1°C higher
than the indirect Aquastat is recommend.

WARNING: Proper control settings must be used
to prevent water supplied for domestic use from
exceeding 130°F, 54°C
or a scald injury will occur!
When higher water temperatures are required
for appliances such as a dishwasher, a mixing
valve or some other tempering means must be
installed. Households with small children may
require water temperatures less than 120°F, 49°C
.
Local codes must be complied with!

Table 6 - Recommend System Temperatures

Hi

Dif

RES

System °F,

°C °F,

°C °F,

°C

Finned Tube Baseboard

190, 88

20, 11.7

85, 29

Cast Iron Radiators

150, 66

20, 11.7

85, 29

Radiant

130, 54

20, 11.7

85, 29

Outdoor Sensor (10K)
The outdoor sensor should be installed to take advantage
of the energy saving features of the Sentry Controller.
Install the sensor on the north, or coldest side of the
building out of direct sun. It must be at least 10 ft, 3 m
from the vent terminal or other source of heat.

Display Data - Input conversion chart

0

50

100

150

200

250

300

350

400

240

215

190

165

140

115

90

65

48

40

LED Display

)

s'

0

0

0(

U

T

B

GT-150

GT-200

GT-400