Links and jumpers, 7 links and jumpers, Input point module (afi5100) – Siemens AFI5100 User Manual

Page 9

Advertising
background image

Input Point Module (AFI5100)

1.7

Links and Jumpers

The following table outlines the link settings for the AFI5100 :

Link Description

Value

LK1, LK2

Links 1 and 2 are used to configure
whether Fire Over-ride (FOR) will oper-
ate in Enhanced FOR mode or Normal.
Enhanced mode also requires the
connection of a supervision circuit to
the Fire Over-ride Input.

To enable Normal
Mode:

LK1 LK2

N

O

R

M

A

L

F

O

R

To enable En-
hanced Mode:

LK1 LK2

N

O

R

M

A

L

F

O

R

LK4, LK6

Links 4 and 6 control whether Fire
Over-ride (FOR) is enabled.
If the links are set to FOR operation,
activation of the FOR input will cause
the outputs to return to the NO position.
If the links are set to the off position,
FOR input will have no effect on the
state of the output relays.

FOR operation
active:

LK4 LK6

F

O

R

E

N

A

B

L

E

FOR operation
ignored:

E

N

A

B

L

E

LK4 LK6

F

O

R

LK3, LK5

These auxiliary links have been included for further enhancement of the system.

LK7

LK7 affects the reset action when the
RESET link (LK9) is set and the power
turned on.
See LK9 below for a description of how
to reset the unit.

LK7

If the jumper on Link 7 is set as shown,
it is set to “Full Reset” mode.

LK7

If the jumper on Link 7 is taken off, it is
set to “Partial Reset” mode.

LK8

This is a General Purpose links that has been included for further enhancement
of the system.

LK9

Memory Clear and Reset
Setting LK9 and turning the power off and on will reset the IPM. A full or partial
reset can be achieved by setting LK7 on or off.
If LK7 is set, the IPM will fully reset and any firmware loaded into the memory will
be erased. You will need to re-program the IPM with firmware again before it can
operate.
If LK7 has the jumper removed, the microcontroller will be rebooted but the firm-
ware will remain in memory.

LK10

EOL Termination (Bus)
This link allows the RS485 BUS com-
munications channel to be terminated
in noisy or lengthy comms.
Note: Units located at the end of bus
lines only should have this link set.

RS485 BUS port
not terminated.

LK10

EOL

RS485 BUS port
terminated.

LK10

EOL

LK11 – LK14

FOR Activation
These links allow FOR activation to be
enabled or disabled for each individual
relay output.
Enabling Fire Override for a relay
means that when the FOR input is
activated, the relay output switch to the
NO position.

LK11

FOR EN

FOR DIS

LK12

In the above diagram LK11 (Relay 1) is
set to FOR Enabled and LK12
(Relay 2) is set to FOR Disabled.

9

Siemens Building Technologies

Fire Safety & Security Products

02.2005